Summary

PREL202011075
Electrical
Finaled
AMERCO REAL ESTATE COMPANY
Alteration/Repair/Replace
PO 36757 F&I fixtures, occupancy sensors, receptacles, photo cell, exit/emergency signs/lights, wall packs, time clock, power fire alarm panel, wire sprinkler flow switch & alarm, overhead door operators, water heaters, thermostats, exhaust fans, dampers, electric water heaters, RTU's, condensing units.
09/22/2020
12/14/2020
02/09/2022
08/13/2021

Locations

Permits

Permit Number: PREL202011075

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 2/25/2021 (8:00 - 10:00) 2/25/2021 (AM) 02/25/2021
Miscellaneous/Other
Comment Only
02/25/2021
Ceiling RI 3rd and 4th

Electrical Rough-in Inspection Partial Pass 3/8/2021 (8:00 - 10:00) 3/8/2021 (AM) 03/08/2021
Miscellaneous/Other
Comment Only
03/08/2021
Ceiling inspection for 2nd and 3rd

Electrical Rough-in Inspection Partial Pass 3/10/2021 (8:00 - 10:00) 3/10/2021 (AM) 03/10/2021
Miscellaneous/Other
Comment Only
03/10/2021
2nd floor ceiling- ok

Electrical Rough-in Inspection Partial Pass 3/11/2021 (8:00 - 10:00) 3/11/2021 (AM) 03/11/2021
Miscellaneous/Other
Comment Only
03/11/2021
UG- ok

Electrical Rough-in Inspection Partial Pass 3/12/2021 (8:00 - 10:00) 3/12/2021 (AM) 03/12/2021
Miscellaneous/Other
Comment Only
03/12/2021
Euffer grounding- ok

Electrical Rough-in Inspection Passed 3/31/2021 (8:00 - 10:00) 3/31/2021 (AM) 03/31/2021
Miscellaneous/Other
Comment Only
03/31/2021
1st floor ceiling RI- ok

Electrical Final Inspection Partial Pass 4/7/2021 (8:00 - 10:00) 4/7/2021 (AM) 04/07/2021
Electrical Rough-in Inspection Partial Pass 4/13/2021 (12:30 - 2:30) 4/13/2021 (PM) 04/13/2021
Miscellaneous/Other
Resolved
04/15/2021
Service inspection: 1. Improper grounding electrode sizing to building frame. Improper bonding jumpers to building metal water piping. Size based on combined area of unfused phase conductors. 1500 KCMIL

Miscellaneous/Other
Resolved
04/15/2021
Bond at CT enclosure.

Miscellaneous/Other
Resolved
04/15/2021
Improper main bonding jumper at service.

Miscellaneous/Other
Resolved
04/15/2021
At 112.5 KVA transformer: Improper equipment bonding jumper size. Size based on the 250 KCMIL conductors. Improper system bonding jumper- size based on the combined area of the derived phase conductors- size per total KCMIL area per phase. Improper GEC size for transformer.

Miscellaneous/Other
Comment Only
04/13/2021
Wall RI OK at showroom and bathrooms.

Miscellaneous/Other
Resolved
04/15/2021
Call for re-inspection of service.

Electrical Rough-in Inspection Partial Pass 4/15/2021 (10:00 - 12:00) 4/15/2021 (AM) 04/15/2021
Miscellaneous/Other
Comment Only
04/15/2021
Trench & UG OK at parking lot for lighting and Tele-Co

Miscellaneous/Other
Comment Only
04/15/2021
Trench & UG OK at parking lot for lighting and Tele-Co

Miscellaneous/Other
Comment Only
04/15/2021
Transformer and service corrections OK. Ok to release the service to Xcel.

Electrical Rough-in Inspection Partial Pass 4/23/2021 (10:00 - 12:00) 4/23/2021 (AM) 04/23/2021
Miscellaneous/Other
Comment Only
04/23/2021
Above ceilings- ok

Electrical Rough-in Inspection Passed 6/2/2021 (8:00 - 10:00) 6/2/2021 (AM) 06/02/2021
Miscellaneous/Other
Comment Only
06/02/2021
Above ceiling- ok

Electrical Final Inspection Partial Pass 6/11/2021 (12:30 - 2:30) 6/11/2021 (PM) 06/11/2021
Miscellaneous/Other
Carried Forward
06/11/2021
Ok to temp occupy office and garage area only. Pending building inspection.

Electrical Final Inspection Not Ready 6/23/2021 (12:30 - 2:30) 6/23/2021 (PM) 06/23/2021
Electrical Final Inspection Partial Pass 7/14/2021 (12:30 - 2:30) 7/14/2021 (PM) 07/14/2021
Miscellaneous/Other
Carried Forward
08/12/2021
Fixture guarding maybe required for outline lighting around windows.

Electrical Final Inspection Passed w/ Conditions 7/27/2021 (10:00 - 12:00) 7/27/2021 (AM) 07/27/2021
Miscellaneous/Other
Resolved
07/27/2021
Ok to temp occupy office and garage area only. Pending building inspection.

Miscellaneous/Other
Outstanding
07/27/2021
Rooftop GFCI require WR rating. T5 lights on sides of show windows require protection. A minimum plastic bulb cover required.

Miscellaneous/Other
Comment Only
07/27/2021
Ok to occupy pending building inspection.

Electrical Final Inspection Passed 8/13/2021 (3:30 - 4:00) 8/13/2021 (PM) 08/13/2021
Miscellaneous/Other
Resolved
08/13/2021
Fixture guarding maybe required for outline lighting around windows.

Miscellaneous/Other
Comment Only
08/13/2021
Final for electrical- ok