Permit Application Status

PREL202012412


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202012412
Electrical
Finaled
MOAC MALL HOLDINGS LLC
Other
ELECTRICAL BUILD OUT HEY JOY E141
10/12/2020
10/16/2020
06/08/2021
12/10/2020

Locations

Permits

Permit Number: PREL202012412

Electrical
Finaled
10/16/2020
06/08/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 10/21/2020 (12:30 - 2:30) 10/21/2020 (PM) 10/21/2020
Corrections:


Miscellaneous/Other
Comment Only
10/21/2020
RI OK @ walls, columns and soffits

Electrical Rough-in Inspection Passed 11/12/2020 (10:00 - 12:00) 11/12/2020 (AM) 11/12/2020
Corrections:


Miscellaneous/Other
Comment Only
11/12/2020
Back of house above ceiling RI OK.

Electrical Rough-in Inspection Failed 11/13/2020
Corrections:


Miscellaneous/Other
Carried Forward
11/13/2020
Site visit- to review electrical for millwork/showcase- Not approved- no NRTL listing for assembly. Improper- makeshift wiring. Power supplies are not limited energy/ class 2. Power supplies are not listed.

Electrical Rough-in Inspection Partial Pass 11/24/2020 (12:30 - 2:30) 11/24/2020 (PM) 11/24/2020
Corrections:


Miscellaneous/Other
Comment Only
11/24/2020
Site visit- to review electrical for millwork/showcase- Not approved- no NRTL listing for assembly. Improper- makeshift wiring. Power supplies are not limited energy/ class 2. Power supplies are not listed.

Miscellaneous/Other
Comment Only
11/24/2020
Partial final. Received multiple P.E. independent 3rd party evaluations. There is a sign and other display's to complete.

Electrical Rough-in Inspection Partial Pass 11/25/2020 (10:00 - 12:00) 11/25/2020 (AM) 11/25/2020
Corrections:


Miscellaneous/Other
Comment Only
11/25/2020
Progress inspection OK- sign OK Received independent 3rd party evaluations. Complete display wiring and evaluations and call for final inspection. Partial pass

Electrical Rough-in Inspection Passed 12/10/2020
Electrical Final Inspection Passed 12/10/2020
Corrections:


Miscellaneous/Other
Comment Only
12/10/2020
Received independent 3rd party evaluations for all unlisted equipment. Final OK. No permit card on site.