Summary

PREL202012908
Electrical
Expired
MOAC MALL HOLDINGS LLC
Alteration/Repair/Replace
ELECTRICAL BUILDOUT FOR M&M STORE BLOOMINGTON
10/19/2020
10/29/2020
10/13/2021

Locations

Permits

Permit Number: PREL202012908

Electrical
Expired
10/29/2020
10/13/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
04/01/2021
Separate inspection: Jones signs- 1. Installation of type CMR cable in return air ceilings. Repair or replace to code. 2. Installation of CMP type cable must be performed by MN State licensed TS or EA contractor- with permit and inspection. 3. Two signs are UL listed but the power supply lacks listing- field installed driver is required to be listed Class 2 and specifically permitted for sign use per the listing.

Miscellaneous/Other
Outstanding
04/01/2021
04/01/2021- Unlisted LED luminaires- not allowed.

Electrical Final Inspection Pending
Electrical Rough-in Inspection Partial Pass 2/4/2021 10/30/2020
Corrections:


Miscellaneous/Other
Comment Only
10/30/2020
2nd Floor wall RI OK- met contractor on site

Electrical Rough-in Inspection Partial Pass 11/24/2020 (12:30 - 2:30) 11/24/2020 (PM) 11/24/2020
Corrections:


Miscellaneous/Other
Comment Only
11/24/2020
Trench/UG inspections OK at multiple locations for floor boxes

Electrical Rough-in Inspection Partial Pass 12/1/2020 (8:00 - 10:00) 12/1/2020 (AM) 12/01/2020
Corrections:


Miscellaneous/Other
Comment Only
12/01/2020
Wall RI- OK

Electrical Rough-in Inspection Partial Pass 12/2/2020 (8:00 - 10:00) 12/2/2020 (AM) 12/02/2020
Corrections:


Miscellaneous/Other
Comment Only
12/02/2020
2nd floor- above ceiling RI at hard lid ceiling- progress inspection

Electrical Rough-in Inspection Partial Pass 12/3/2020 (8:00 - 10:00) 12/3/2020 (AM) 12/03/2020
Corrections:


Miscellaneous/Other
Comment Only
12/03/2020
Partial- progress inspection for RI for lighting/ above hard lid ceiling second floor

Electrical Rough-in Inspection Partial Pass 12/4/2020 (8:00 - 10:00) 12/4/2020 (AM) 12/04/2020
Corrections:


Miscellaneous/Other
Comment Only
12/04/2020
RI 2nd floor - progress inspection for above hard lid ceilings. Bathrooms and corridor OK.

Electrical Rough-in Inspection Not Ready 12/7/2020 (8:00 - 10:00) 12/7/2020 (AM) 12/07/2020
Electrical Rough-in Inspection Partial Pass 12/8/2020 (8:00 - 10:00) 12/8/2020 (AM) 12/08/2020
Corrections:


Miscellaneous/Other
Comment Only
12/08/2020
Progress inspection OK

Electrical Rough-in Inspection Partial Pass 12/9/2020 (8:00 - 10:00) 12/9/2020 (AM) 12/09/2020
Corrections:


Miscellaneous/Other
Comment Only
12/09/2020
Remainder of hard lid ceiling on 2nd floor RI OK

Electrical Rough-in Inspection Partial Pass 12/10/2020 12/10/2020 (AM) 12/10/2020
Corrections:


Miscellaneous/Other
Comment Only
12/10/2020
Progress inspection- 1st floor above hard lid at "horseshoe"- OK

Electrical Rough-in Inspection Partial Pass 12/11/2020 (8:00 - 10:00) 12/11/2020 (AM) 12/11/2020
Corrections:


Miscellaneous/Other
Comment Only
12/11/2020
site visit OK

Electrical Rough-in Inspection Partial Pass 12/15/2020 (10:00 - 12:00) 12/15/2020 (AM) 12/15/2020
Corrections:


Miscellaneous/Other
Comment Only
12/15/2020
Progress inspection - 1st floor hard lid RI OK for lighting

Electrical Rough-in Inspection Partial Pass 12/16/2020 (8:00 - 10:00) 12/16/2020 (AM) 12/16/2020
Corrections:


Miscellaneous/Other
Comment Only
12/16/2020
Progress inspection- above hard lid at first floor. Wall RI OK @ 3rd floor.

Electrical Rough-in Inspection Partial Pass 12/17/2020 (8:00 - 10:00) 12/17/2020 (AM) 12/17/2020
Electrical Rough-in Inspection Not Ready 12/18/2020 (8:00 - 10:00) 12/18/2020 (AM) 12/18/2020
Electrical Rough-in Inspection Partial Pass 12/22/2020 (8:00 - 10:00) 12/22/2020 (AM) 12/22/2020
Corrections:


Miscellaneous/Other
Comment Only
12/22/2020
Progress inspection ok- RI at TV walls- OK

Electrical Rough-in Inspection Partial Pass 01/13/2021
Corrections:


Miscellaneous/Other
Comment Only
01/13/2021
Progress inspection- back of house- office and conference room wall RI OK

Electrical Rough-in Inspection Partial Pass 1/19/2021 (2:30 - 3:30) 1/19/2021 (PM) 01/19/2021
Corrections:


Miscellaneous/Other
Comment Only
01/19/2021
Wall RI OK at first level back of house. Wall RI OK at lower level storage

Electrical Rough-in Inspection Partial Pass 1/22/2021 (10:00 - 12:00) 1/22/2021 (AM) 01/22/2021
Corrections:


Miscellaneous/Other
Comment Only
01/22/2021
2nd floor - back of house above drop ceiling- OK

Electrical Rough-in Inspection Partial Pass 2/4/2021 (8:00 - 10:00) 2/4/2021 (AM) 02/04/2021
Corrections:


Miscellaneous/Other
Comment Only
02/04/2021
Questions at site- transformer installation

Electrical Rough-in Inspection Partial Pass 02/25/2021
Corrections:


Miscellaneous/Other
Comment Only
02/25/2021
Above ceiling back of house 1st floor.- OK Above ceiling at lower storage and conference room- OK

Electrical Rough-in Inspection Partial Pass 3/10/2021 (8:00 - 10:00) 3/10/2021 (AM) 03/10/2021
Corrections:


Miscellaneous/Other
Comment Only
03/10/2021
Partial final - OK at lower level storage area

Electrical Rough-in Inspection Failed 3/19/2021 (12:30 - 2:30) 3/19/2021 (PM) 03/22/2021
Corrections:


Miscellaneous/Other
Carried Forward
03/22/2021
1. Non plenum cables installed in a return air space.

Miscellaneous/Other
Carried Forward
03/22/2021
2. Non listed- Class 1 type power supplies installed- improper sized wiring methods and cable sizing installed. Improper wiring in listed sign assembly based on power supply type. Note - the control apparatus for each sign had been mounted to the sign mounting bracket- this had been relocated to a 4 square J-box by the electrical contractor in an effort to mitigate the Class 1 power source.

Miscellaneous/Other
Carried Forward
03/22/2021
3. #12 AWG MC cable not permitted on a 41 amp output DC power supply. Note -supply is unlisted and considered a Class 1 power circuit.

Miscellaneous/Other
Carried Forward
03/22/2021
At light tunnel: Unlisted Class 1 power supply. Factory wiring methods are set up for limited energy installation only.

Miscellaneous/Other
Carried Forward
03/22/2021
Provide all installation instructions. Note: any replacement of drivers/power supplies must comply with: NEC 600. 24 Listed for use with signs and must be accompanied by the manufacturers installation instructions.

Miscellaneous/Other
Carried Forward
03/22/2021
Call for re-inspection.

Electrical Rough-in Inspection Failed 3/26/2021 (8:00 - 10:00) 3/26/2021 (AM) 03/26/2021
Corrections:


Miscellaneous/Other
Carried Forward
03/26/2021
1. Non plenum cables installed in a return air space.

Miscellaneous/Other
Carried Forward
03/26/2021
2. Non listed- Class 1 type power supplies installed- improper sized wiring methods and cable sizing installed. Improper wiring in listed sign assembly based on power supply type. Note - the control apparatus for each sign had been mounted to the sign mounting bracket- this had been relocated to a 4 square J-box by the electrical contractor in an effort to mitigate the Class 1 power source.

Miscellaneous/Other
Carried Forward
03/26/2021
3. #12 AWG MC cable not permitted on a 41 amp output DC power supply. Note -supply is unlisted and considered a Class 1 power circuit.

Miscellaneous/Other
Carried Forward
03/26/2021
At light tunnel: Unlisted Class 1 power supply. Factory wiring methods are set up for limited energy installation only.

Miscellaneous/Other
Carried Forward
03/26/2021
Provide all installation instructions. Note: any replacement of drivers/power supplies must comply with: NEC 600. 24 Listed for use with signs and must be accompanied by the manufacturers installation instructions.

Miscellaneous/Other
Carried Forward
03/26/2021
Call for re-inspection.

Miscellaneous/Other
Carried Forward
03/26/2021
Separate inspection: Jones signs- 1. Installation of type CMR cable in return air ceilings. Repair or replace to code. 2. Installation of CMP type cable must be performed by MN State licensed TS or EA contractor- with permit and inspection. 3. Two signs are UL listed but the power supply lacks listing- field installed driver is required to be listed Class 2 and specifically permitted for sign use per the listing.

Electrical Rough-in Inspection Failed 04/01/2021
Corrections:


Miscellaneous/Other
Comment Only
04/01/2021
1. Non plenum cables installed in a return air space.

Miscellaneous/Other
Comment Only
04/01/2021
2. Non listed- Class 1 type power supplies installed- improper sized wiring methods and cable sizing installed. Improper wiring in listed sign assembly based on power supply type. Note - the control apparatus for each sign had been mounted to the sign mounting bracket- this had been relocated to a 4 square J-box by the electrical contractor in an effort to mitigate the Class 1 power source.

Miscellaneous/Other
Comment Only
04/01/2021
3. #12 AWG MC cable not permitted on a 41 amp output DC power supply. Note -supply is unlisted and considered a Class 1 power circuit.

Miscellaneous/Other
Comment Only
04/01/2021
At light tunnel: Unlisted Class 1 power supply. Factory wiring methods are set up for limited energy installation only.

Miscellaneous/Other
Comment Only
04/01/2021
Provide all installation instructions. Note: any replacement of drivers/power supplies must comply with: NEC 600. 24 Listed for use with signs and must be accompanied by the manufacturers installation instructions.

Miscellaneous/Other
Resolved
04/01/2021
Call for re-inspection.

Miscellaneous/Other
Carried Forward
04/01/2021
Separate inspection: Jones signs- 1. Installation of type CMR cable in return air ceilings. Repair or replace to code. 2. Installation of CMP type cable must be performed by MN State licensed TS or EA contractor- with permit and inspection. 3. Two signs are UL listed but the power supply lacks listing- field installed driver is required to be listed Class 2 and specifically permitted for sign use per the listing.

Miscellaneous/Other
Carried Forward
04/01/2021
04/01/2021- Unlisted LED luminaires- not allowed.

Electrical Final Inspection Partial Pass 4/8/2021 (12:30 - 2:30) 4/8/2021 (PM) 04/08/2021
Corrections:


Miscellaneous/Other
Comment Only
04/08/2021
Partial final- egress lighting OK. Preliminary walk through OK. Provide independent 3rd party evaluations for unlisted equipment and for listed assemblies that were field altered. Complete all installations- call for final.

Electrical Final Inspection Not Ready 4/9/2021 (12:30 - 2:30) 4/9/2021 (PM) 04/09/2021
Electrical Final Inspection Passed 4/16/2021 (12:30 - 2:30) 4/16/2021 (PM) 04/16/2021
Corrections:


Miscellaneous/Other
Comment Only
04/16/2021
Independent 3rd party evaluations received. Final OK.