Permit Application Status

PREL202100961


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202100961
Electrical
Finaled
FRIENDLY PALM HOSPITALITY LLC
Alteration/Repair/Replace
Installing a Manhole Level Monitoring Control Panel with a Single Phase 120/240 Volt 60 Amp Service.
01/29/2021
02/03/2021
12/06/2021
06/09/2021

Locations

Permits

Permit Number: PREL202100961

Electrical
Finaled
02/03/2021
12/06/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Passed w/ Conditions 6/9/2021 (12:30 - 2:30) 6/9/2021 (PM) 06/09/2021
Corrections:


Miscellaneous/Other
Comment Only
06/09/2021
Met contractor on site- verbal corrections: 1. Install locknut at rigid metal conduit at meter enclosure - service conductor raceway. 2. Install arc flash warning label, install available fault current label & label main as service disconnect means. 3. Label the intrinsically safe raceway. Service released to Xcel. Email photos to: tmiller@bloomingtonmn.gov