PREL202101436
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Failed | 3/9/2021 (8:00 - 10:00) | 3/9/2021 (AM) | 03/09/2021 |
Corrections:
Miscellaneous/Other
Carried Forward
03/09/2021
LFMC needs to be bonded, supply side bonding jumper. Per NEC 230.43
|
||||
Miscellaneous/Other
Carried Forward
03/09/2021
Available fault currents need for equipment use on service.
|
||||
Miscellaneous/Other
Carried Forward
03/09/2021
Trailer needs GEC installed.
Spoke with contractor for corrections needed call when service ready.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/11/2021 (10:00 - 12:00) | 3/11/2021 (AM) | 03/11/2021 |
Corrections:
Miscellaneous/Other
Resolved
03/11/2021
LFMC needs to be bonded, supply side bonding jumper. Per NEC 230.43
|
||||
Miscellaneous/Other
Resolved
03/11/2021
Available fault currents need for equipment use on service.
|
||||
Miscellaneous/Other
Resolved
03/11/2021
Trailer needs GEC installed.
Spoke with contractor for corrections needed call when service ready.
|
||||
Miscellaneous/Other
Comment Only
03/11/2021
Issues resolved for temp service, released to Xcel
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/5/2021 (8:00 - 10:00) | 4/5/2021 (AM) | 04/05/2021 |
Corrections:
Miscellaneous/Other
Comment Only
04/05/2021
UG inside building- ok
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/13/2021 (8:00 - 10:00) | 7/13/2021 (AM) | 07/13/2021 |
Corrections:
Miscellaneous/Other
Comment Only
07/13/2021
Wall RI- ok
FA permit required for subcontractor
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/17/2021 (8:00 - 10:00) | 9/17/2021 (AM) | 09/20/2021 |
Corrections:
Miscellaneous/Other
Comment Only
09/20/2021
Service approved for connection. Xcel contacted.
|
||||
Miscellaneous/Other
Carried Forward
09/20/2021
Pictures required for proper bonding of CT can.
Available fault current labeling required before final on all panels including service.
|
||||
Electrical Rough-in Inspection | Passed | 10/8/2021 (8:00 - 10:00) | 10/8/2021 (AM) | 10/08/2021 |
Corrections:
Miscellaneous/Other
Resolved
10/08/2021
Pictures required for proper bonding of CT can.
Available fault current labeling required before final on all panels including service.
|
||||
Miscellaneous/Other
Outstanding
10/08/2021
Available fault current labeling needed.
|
||||
Miscellaneous/Other
Comment Only
10/08/2021
Above ceilings- ok
|
||||
Electrical Final Inspection | Partial Pass | 10/29/2021 (2:30 - 3:30) | 10/29/2021 (PM) | 10/29/2021 |
Corrections:
Miscellaneous/Other
Carried Forward
10/29/2021
Controlled receptacles required to be labeled per NEC 406.3E
|
||||
Miscellaneous/Other
Carried Forward
10/29/2021
GFCI required for receptacles by slop sink and microwave.
|
||||
Miscellaneous/Other
Carried Forward
10/29/2021
FA labeling needed for CB and panel.
|
||||
Miscellaneous/Other
Carried Forward
10/29/2021
2 rooftop GFCI no power.
|
||||
Miscellaneous/Other
Carried Forward
10/29/2021
Available fault current labeling needed for service, panels, and HVAC units. Labels must meet 110.24 and 110.16B requirements.
Arc flash warning labels needed on appropriate equipment.
|
||||
Electrical Final Inspection | Passed | 11/10/2021 (2:30 - 3:30) | 11/10/2021 (PM) | 11/10/2021 |
Corrections:
Miscellaneous/Other
Resolved
11/10/2021
Controlled receptacles required to be labeled per NEC 406.3E
|
||||
Miscellaneous/Other
Resolved
11/10/2021
GFCI required for receptacles by slop sink and microwave.
|
||||
Miscellaneous/Other
Resolved
11/10/2021
FA labeling needed for CB and panel.
|
||||
Miscellaneous/Other
Resolved
11/10/2021
2 rooftop GFCI no power.
|
||||
Miscellaneous/Other
Resolved
11/10/2021
Available fault current labeling needed for service, panels, and HVAC units. Labels must meet 110.24 requirements.
Arc flash warning labels needed on appropriate equipment.
|