Summary

PREL202102592
Electrical
Finaled
INTERNATIONAL PLAZA
Alteration/Repair/Replace
PROVIDE LIGHTING AND POWER ALTERATIONS FOR ELEVATOR MODERNIZATION
03/15/2021
03/15/2021
10/26/2022
04/29/2022

Locations

Permits

Permit Number: PREL202102592

Electrical
Finaled
03/15/2021
10/26/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Failed 1/31/2022 (12:30 - 2:30) 1/31/2022 (PM) 02/01/2022
Corrections:


Miscellaneous/Other
Carried Forward
02/01/2022
Verify & document available fault current at ATS Verify ATS is within the SCCR rating- based on available fault current Install arc flash warning labels to code Existing installations- if any alterations to OCP size or type label accordingly If any alterations to OCP- verify selective coordination

Electrical Final Inspection Passed 04/29/2022
Corrections:


Miscellaneous/Other
Resolved
04/29/2022
Verify & document available fault current at ATS Verify ATS is within the SCCR rating- based on available fault current Install arc flash warning labels to code Existing installations- if any alterations to OCP size or type label accordingly If any alterations to OCP- verify selective coordination