PREL202102592
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Failed | 1/31/2022 (12:30 - 2:30) | 1/31/2022 (PM) | 02/01/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
02/01/2022
Verify & document available fault current at ATS
Verify ATS is within the SCCR rating- based on available fault current
Install arc flash warning labels to code
Existing installations- if any alterations to OCP size or type label accordingly
If any alterations to OCP- verify selective coordination
|
||||
Electrical Final Inspection | Passed | 04/29/2022 | ||
Corrections:
Miscellaneous/Other
Resolved
04/29/2022
Verify & document available fault current at ATS
Verify ATS is within the SCCR rating- based on available fault current
Install arc flash warning labels to code
Existing installations- if any alterations to OCP size or type label accordingly
If any alterations to OCP- verify selective coordination
|