PREL202106501
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 7/14/2021 (8:00 - 10:00) | 7/14/2021 (AM) | 07/15/2021 |
Corrections:
Miscellaneous/Other
Comment Only
07/15/2021
Progress inspection OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/22/2021 (8:00 - 10:00) | 7/22/2021 (AM) | 07/22/2021 |
Corrections:
Miscellaneous/Other
Comment Only
07/22/2021
Site visit with building inspector-
progress inspection OK
|
||||
Electrical Rough-in Inspection | Passed | 8/11/2021 (8:00 - 10:00) | 8/11/2021 (AM) | 08/13/2021 |
Corrections:
Miscellaneous/Other
Comment Only
08/13/2021
Project completed.
Verbal to contractor- complete the bonding of the telescoping wireway between the transformer and existing switch. Equipment bonding jumper to sized based on the Kcmil area of the transformer secondary conductors.
|
||||
Electrical Final Inspection | Passed | 9/1/2021 (8:00 - 10:00) | 9/1/2021 (AM) | 09/02/2021 |