PREL202107020


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202107020
Electrical
Finaled
94 LYNDALE LLC
Alteration/Repair/Replace
Renovate existing restaurant. (Exterior work on different permit. 6/10/2021 )(Not doing exterior work, only changing light bulbs in the lights outside.) SNT
06/08/2021
06/09/2021
04/03/2022
10/05/2021

Locations

Permits

Permit Number: PREL202107020

Electrical
Finaled
06/09/2021
04/03/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 6/14/2021 (8:00 - 10:00) 6/14/2021 (AM) 06/14/2021
Corrections:


Miscellaneous/Other
Comment Only
06/14/2021
Wall RI only- ok

Electrical Rough-in Inspection Passed 7/9/2021 (12:30 - 2:30) 7/9/2021 (PM) 07/09/2021
Corrections:


Miscellaneous/Other
Comment Only
07/09/2021
Above ceiling RI OK for power & light

Electrical Final Inspection Failed 7/26/2021 (2:30 - 3:30) 7/26/2021 (PM) 07/26/2021
Corrections:


Miscellaneous/Other
Carried Forward
07/26/2021
GFCI needed for all 120v receptacles in kitchen area.

Miscellaneous/Other
Carried Forward
07/26/2021
New panel available fault currents need proper equipment for amour available.

Miscellaneous/Other
Carried Forward
07/26/2021
Need to see rooftop.

Miscellaneous/Other
Carried Forward
07/26/2021
Verify listings of new installed signs and outline lighting.

Electrical Final Inspection Partial Pass 7/30/2021 (10:00 - 12:00) 7/30/2021 (AM) 07/30/2021
Corrections:


Miscellaneous/Other
Comment Only
07/30/2021
Interior final- ok for temp occupancy. Waiting for proper main breaker to be installed for series rating of Siemens panel Also need proper listing and labeling of outline lighting, this will be moved to separate permit under exterior lighting.

Electrical Final Inspection Passed 10/05/2021
Corrections:


Miscellaneous/Other
Resolved
10/05/2021
GFCI needed for all 120v receptacles in kitchen area.

Miscellaneous/Other
Resolved
10/05/2021
New panel available fault currents need proper equipment for amour available.

Miscellaneous/Other
Resolved
10/05/2021
Need to see rooftop.

Miscellaneous/Other
Resolved
10/05/2021
Verify listings of new installed signs and outline lighting.

Miscellaneous/Other
Comment Only
10/05/2021
Series rating for new panel- ok Exterior lighting on separate permit.