PREL202107020
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Rough-in Inspection | Partial Pass | 6/14/2021 (8:00 - 10:00) | 6/14/2021 (AM) | 06/14/2021 |
|
Corrections:
Miscellaneous/Other
Comment Only
06/14/2021
Wall RI only- ok
|
||||
| Electrical Rough-in Inspection | Passed | 7/9/2021 (12:30 - 2:30) | 7/9/2021 (PM) | 07/09/2021 |
|
Corrections:
Miscellaneous/Other
Comment Only
07/09/2021
Above ceiling RI OK for power & light
|
||||
| Electrical Final Inspection | Failed | 7/26/2021 (2:30 - 3:30) | 7/26/2021 (PM) | 07/26/2021 |
|
Corrections:
Miscellaneous/Other
Carried Forward
07/26/2021
GFCI needed for all 120v receptacles in kitchen area.
|
||||
|
Miscellaneous/Other
Carried Forward
07/26/2021
New panel available fault currents need proper equipment for amour available.
|
||||
|
Miscellaneous/Other
Carried Forward
07/26/2021
Need to see rooftop.
|
||||
|
Miscellaneous/Other
Carried Forward
07/26/2021
Verify listings of new installed signs and outline lighting.
|
||||
| Electrical Final Inspection | Partial Pass | 7/30/2021 (10:00 - 12:00) | 7/30/2021 (AM) | 07/30/2021 |
|
Corrections:
Miscellaneous/Other
Comment Only
07/30/2021
Interior final- ok for temp occupancy.
Waiting for proper main breaker to be installed for series rating of Siemens panel
Also need proper listing and labeling of outline lighting, this will be moved to separate permit under exterior lighting.
|
||||
| Electrical Final Inspection | Passed | 10/05/2021 | ||
|
Corrections:
Miscellaneous/Other
Resolved
10/05/2021
GFCI needed for all 120v receptacles in kitchen area.
|
||||
|
Miscellaneous/Other
Resolved
10/05/2021
New panel available fault currents need proper equipment for amour available.
|
||||
|
Miscellaneous/Other
Resolved
10/05/2021
Need to see rooftop.
|
||||
|
Miscellaneous/Other
Resolved
10/05/2021
Verify listings of new installed signs and outline lighting.
|
||||
|
Miscellaneous/Other
Comment Only
10/05/2021
Series rating for new panel- ok
Exterior lighting on separate permit.
|
||||