Permit Application Status

PREL202107558


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202107558
Electrical
Finaled
CITY OF BLOOMINGTON
Other
TENANT FINISH COMPLETE ELECTRICAL WIRING.
06/17/2021
07/26/2021
01/04/2023
07/08/2022

Locations

Permits

Permit Number: PREL202107558

Electrical
Finaled
07/26/2021
01/04/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 7/30/2021 (8:00 - 10:00) 7/30/2021 (AM) 07/30/2021
Corrections:


Miscellaneous/Other
Comment Only
07/30/2021
Under ground by water main - ok PVC stubbed through footing in same area- ok

Electrical Rough-in Inspection Partial Pass 11/15/2021 (10:00 - 12:00) 11/15/2021 (AM) 11/16/2021
Corrections:


Miscellaneous/Other
Comment Only
11/16/2021
Site visit OK. UG / trench- partial- photos and on-site OK 2nd level slab for office area- OK

Electrical Rough-in Inspection Partial Pass 12/7/2021 (8:00 - 10:00) 12/7/2021 (AM) 12/07/2021
Underground Inspection
Corrections:


Miscellaneous/Other
Comment Only
12/07/2021
Progress inspection for UG - RI OK

Electrical Rough-in Inspection Partial Pass 1/10/2022 (8:00 - 10:00) 1/10/2022 (AM) 01/10/2022
Corrections:


Miscellaneous/Other
Comment Only
01/10/2022
First floor office walls - RI OK

Electrical Rough-in Inspection Partial Pass 1/31/2022 (8:00 - 10:00) 1/31/2022 (AM) 01/31/2022
Corrections:


Miscellaneous/Other
Comment Only
01/31/2022
Wall RI OK at north offices

Miscellaneous/Other
Comment Only
01/31/2022
Preliminary review of service equipment Verify GFPE testing

Electrical Rough-in Inspection Partial Pass 2/11/2022 (12:30 - 2:30) 2/11/2022 (PM) 02/11/2022
Corrections:


Miscellaneous/Other
Comment Only
02/11/2022
Bathrooms- RI OK

Electrical Rough-in Inspection Partial Pass 2/17/2022 (10:00 - 12:00) 2/17/2022 (AM) 02/17/2022
Corrections:


Miscellaneous/Other
Comment Only
02/17/2022
Above ceiling RI OK at upper level drop ceilings.

Miscellaneous/Other
Carried Forward
02/17/2022
Shade control cabinet lacks an NRTL listing as an assembly. The power supply is individually listed. The Listed power supply IS NOT Class 2. There is a circuit board - that may limit the output power- no NRTL. Wiring method installed requires listed Class 2 power supply. NOT APPROVED

Electrical Rough-in Inspection Partial Pass 3/7/2022 (8:00 - 10:00) 3/7/2022 (AM) 03/07/2022
Corrections:


Miscellaneous/Other
Carried Forward
03/07/2022
Shade control cabinet lacks an NRTL listing as an assembly. The power supply is individually listed. The Listed power supply IS NOT Class 2. There is a circuit board - that may limit the output power- no NRTL. Wiring method installed requires listed Class 2 power supply. NOT APPROVED

Miscellaneous/Other
Comment Only
03/07/2022
Service OK to release to Xcel. Install all required labeling, including available fault current.

Miscellaneous/Other
Carried Forward
03/07/2022
Verify - equipment grounding sizing for future gen-set and transfer switch. Size EGC on OCP device. Based on 1600 AMP OCP- minimum EGC- 350 AL or 4/0 copper. Verify pipe fill.

Miscellaneous/Other
Carried Forward
03/07/2022
Verify available fault current at EM_ ( life-safety ) transfer switch. See manufacturer chart- SCCR rating is specific to brand, size and frame type OCP protecting transfer switch.

Electrical Rough-in Inspection Partial Pass 3/17/2022 (8:00 - 10:00) 3/17/2022 (AM) 03/17/2022
Corrections:


Miscellaneous/Other
Resolved
03/17/2022
Shade control cabinet lacks an NRTL listing as an assembly. The power supply is individually listed. The Listed power supply IS NOT Class 2. There is a circuit board - that may limit the output power- no NRTL. Wiring method installed requires listed Class 2 power supply. NOT APPROVED

Miscellaneous/Other
Resolved
03/17/2022
Verify - equipment grounding sizing for future gen-set and transfer switch. Size EGC on OCP device. Based on 1600 AMP OCP- minimum EGC- 350 AL or 4/0 copper. Verify pipe fill.

Miscellaneous/Other
Resolved
03/17/2022
Verify available fault current at EM_ ( life-safety ) transfer switch. See manufacturer chart- SCCR rating is specific to brand, size and frame type OCP protecting transfer switch.

Miscellaneous/Other
Comment Only
03/17/2022
NE offices & labs ceiling RI

Miscellaneous/Other
Carried Forward
03/17/2022
Improper working clearance at VAV boxes- sprinkler piping in front of power enclosure

Miscellaneous/Other
Carried Forward
03/17/2022
Class 2 power cable introduced into power enclosure ( handy box ) at transfer fans. See separate email.

Electrical Rough-in Inspection Partial Pass 3/24/2022 (10:00 - 12:00) 3/24/2022 (AM) 03/24/2022
Corrections:


Miscellaneous/Other
Carried Forward
03/24/2022
Improper working clearance at VAV boxes- sprinkler piping in front of power enclosure

Miscellaneous/Other
Carried Forward
03/24/2022
Class 2 power cable introduced into power enclosure ( handy box ) at transfer fans. See separate email.

Miscellaneous/Other
Comment Only
03/24/2022
RTU -roof top inspection OK. Label available fault current at units. All units reviewed today have a 65K SCCR Call for inspection for small condensing unit and mini-splits when ready. Verify/label available fault current at these units.

Electrical Rough-in Inspection Passed 4/20/2022 (10:00 - 12:00) 4/20/2022 (AM) 04/20/2022
Corrections:


Miscellaneous/Other
Resolved
04/20/2022
Improper working clearance at VAV boxes- sprinkler piping in front of power enclosure

Miscellaneous/Other
Resolved
04/20/2022
Class 2 power cable introduced into power enclosure ( handy box ) at transfer fans. See separate email.

Miscellaneous/Other
Comment Only
04/20/2022
Progress inspection OK. Clearance issue above ceiling - correction OK. Class 2 wiring at transfer fans- Correction -OK

Electrical Final Inspection Partial Pass 5/26/2022 (8:00 - 10:00) 5/26/2022 (AM) 05/26/2022
Corrections:


Miscellaneous/Other
Carried Forward
05/26/2022
Life Safety Generator start time required to be less than 10 sec., First test was 14 sec.

Miscellaneous/Other
Carried Forward
05/26/2022
Panel covers missing in a couple electric rooms. These are in locked spaces.

Miscellaneous/Other
Carried Forward
05/26/2022
50a feeds for dishwashers require GFCI protection from a listed class A device. Current protection is not a listed device, only a listed component..

Miscellaneous/Other
Carried Forward
05/26/2022
All furniture wiring required to be completed by a licensed electrical contractor. Talked with job sup to have furniture installers leave the work for electrical to complete. Contractor to go through work already completed and verify unlicensed work.

Miscellaneous/Other
Comment Only
05/26/2022
Temporary OCC ok, if generator test passes building inspector, and Fire Marshall test.

Electrical Final Inspection Passed 7/7/2022 (8:00 - 10:00) 7/7/2022 (AM) 07/08/2022
Corrections:


Miscellaneous/Other
Resolved
07/08/2022
Life Safety Generator start time required to be less than 10 sec., First test was 14 sec.

Miscellaneous/Other
Resolved
07/08/2022
Panel covers missing in a couple electric rooms. These are in locked spaces.

Miscellaneous/Other
Resolved
07/08/2022
50a feeds for dishwashers require GFCI protection from a listed class A device. Current protection is not a listed device, only a listed component..

Miscellaneous/Other
Resolved
07/08/2022
All furniture wiring required to be completed by a licensed electrical contractor. Talked with job sup to have furniture installers leave the work for electrical to complete. Contractor to go through work already completed and verify unlicensed work.

Miscellaneous/Other
Comment Only
07/08/2022
Issues resolved, open items moved to new permit.