PREL202109270
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Pending | |||
|
Corrections:
Miscellaneous/Other
Outstanding
09/16/2021
Meet with contact person at the school- inspector needs to meet contractor on site for re-inspection and to confirm conduit run paths and to verify panelboard location.
|
||||
|
Miscellaneous/Other
Outstanding
09/16/2021
Install HVAC service receptacles to code- 25" of unit(s).
Loose fittings at seal-tight runs into mini-split unit at roof.
Improper equipment grounding at disconnect means- bond ( pigtail ) equipment grounding conductor to enclosure(s).
No labeling of panel directory- ( based on panelboard viewed at inspection )
Verify fire stopping at concrete block wall at conduit run.
Call for re-inspection.
|
||||
| Electrical Final Inspection | Failed | 9/16/2021 (10:00 - 12:00) | 9/16/2021 (AM) | 09/16/2021 |
| 8/3/21 inspection cancelled. jms | ||||
|
Corrections:
Miscellaneous/Other
Carried Forward
09/16/2021
Meet with contact person at the school- inspector needs to meet contractor on site for re-inspection and to confirm conduit run paths and to verify panelboard location.
|
||||
|
Miscellaneous/Other
Carried Forward
09/16/2021
Install HVAC service receptacles to code- 25" of unit(s).
Loose fittings at seal-tight runs into mini-split unit at roof.
Improper equipment grounding at disconnect means- bond ( pigtail ) equipment grounding conductor to enclosure(s).
No labeling of panel directory- ( based on panelboard viewed at inspection )
Verify fire stopping at concrete block wall at conduit run.
Call for re-inspection.
|
||||