Permit Application Status

PREL202109270


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202109270
Electrical
Expired
AL JAZARI INSTITUTE PROPERTY LLC
Alteration/Repair/Replace
Electrical side for 4 mini-split heat a/c units
07/20/2021
07/26/2021
03/15/2022

Locations

Permits

Permit Number: PREL202109270

Electrical
Expired
07/26/2021
03/15/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
09/16/2021
Meet with contact person at the school- inspector needs to meet contractor on site for re-inspection and to confirm conduit run paths and to verify panelboard location.

Miscellaneous/Other
Outstanding
09/16/2021
Install HVAC service receptacles to code- 25" of unit(s). Loose fittings at seal-tight runs into mini-split unit at roof. Improper equipment grounding at disconnect means- bond ( pigtail ) equipment grounding conductor to enclosure(s). No labeling of panel directory- ( based on panelboard viewed at inspection ) Verify fire stopping at concrete block wall at conduit run. Call for re-inspection.

Electrical Final Inspection Failed 9/16/2021 (10:00 - 12:00) 9/16/2021 (AM) 09/16/2021
8/3/21 inspection cancelled. jms
Corrections:


Miscellaneous/Other
Carried Forward
09/16/2021
Meet with contact person at the school- inspector needs to meet contractor on site for re-inspection and to confirm conduit run paths and to verify panelboard location.

Miscellaneous/Other
Carried Forward
09/16/2021
Install HVAC service receptacles to code- 25" of unit(s). Loose fittings at seal-tight runs into mini-split unit at roof. Improper equipment grounding at disconnect means- bond ( pigtail ) equipment grounding conductor to enclosure(s). No labeling of panel directory- ( based on panelboard viewed at inspection ) Verify fire stopping at concrete block wall at conduit run. Call for re-inspection.