Permit Application Status

PREL202110037


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202110037
Electrical
Finaled
GKII NORTHLAND CENTER LLC
Alteration/Repair/Replace
Remodel for tenant.
08/02/2021
08/03/2021
04/24/2022
10/26/2021

Locations

Permits

Permit Number: PREL202110037

Electrical
Finaled
08/03/2021
04/24/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Failed 9/20/2021 (2:30 - 3:30) 9/20/2021 (PM) 09/20/2021
Corrections:


Miscellaneous/Other
Carried Forward
09/20/2021
KO seals needed in the south end area.

Miscellaneous/Other
Carried Forward
09/20/2021
Properly support disconnect for VAV in north end of area.

Miscellaneous/Other
Carried Forward
09/20/2021
Floor receptacle laying on ceiling by VAV in south end.

Miscellaneous/Other
Carried Forward
09/20/2021
MC requires proper support along office walls.

Electrical Rough-in Inspection Failed 9/30/2021 (12:30 - 2:30) 9/30/2021 (PM) 09/30/2021
Corrections:


Miscellaneous/Other
Resolved
09/30/2021
KO seals needed in the south end area.

Miscellaneous/Other
Resolved
09/30/2021
Properly support disconnect for VAV in north end of area.

Miscellaneous/Other
Resolved
09/30/2021
Floor receptacle laying on ceiling by VAV in south end.

Miscellaneous/Other
Resolved
09/30/2021
MC requires proper support along office walls.

Miscellaneous/Other
Carried Forward
09/30/2021
Non plenum rated condensate pump installed above ceiling with cord. Neither can be installed above ceiling in a plenum space. Spoke with contractor and left a message for job superintendent.

Electrical Rough-in Inspection Passed 10/26/2021 (2:30 - 3:30) 10/26/2021 (PM) 10/26/2021
Corrections:


Miscellaneous/Other
Resolved
10/26/2021
Non plenum rated condensate pump installed above ceiling with cord. Neither can be installed above ceiling in a plenum space. Spoke with contractor and left a message for job superintendent.

Electrical Final Inspection Passed 10/26/2021
Corrections:


Miscellaneous/Other
Comment Only
10/26/2021
White box space only no tenant, furniture or casework installed Final- ok