Permit Application Status

PREL202110984


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202110984
Electrical
Expired
JBC BLOOMINGTON LLC
Alteration/Repair/Replace
Air condtioner replacement
08/18/2021
08/25/2021
08/01/2022

Locations

Permits

Permit Number: PREL202110984

Electrical
Expired
08/25/2021
08/01/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
02/02/2022
Remove limited energy conductors from the power raceway "whip". Verify equipment grounding conductor installed at A/C whip.

Electrical Final Inspection Failed 9/7/2021 (10:00 - 12:00) 9/7/2021 (AM) 09/07/2021
Corrections:


Miscellaneous/Other
Carried Forward
09/07/2021
Remove limited energy conductors from the power raceway "whip". Install equipment grounding conductor at the whip from disconnect means to the A/C unit. Secure the power "whip" to code. Call for re-inspection.

Electrical Final Inspection Failed 9/24/2021 (12:30 - 2:30) 9/24/2021 (PM) 09/24/2021
Corrections:


Miscellaneous/Other
Carried Forward
09/24/2021
Remove limited energy conductors from the power raceway "whip". Install equipment grounding conductor at the whip from disconnect means to the A/C unit. Secure the power "whip" to code. Call for re-inspection.

Miscellaneous/Other
Carried Forward
09/24/2021
Correction not made yet.

Electrical Final Inspection Failed 2/2/2022 (10:00 - 12:00) 2/2/2022 (AM) 02/02/2022
Corrections:


Miscellaneous/Other
Comment Only
02/02/2022
Remove limited energy conductors from the power raceway "whip". Install equipment grounding conductor at the whip from disconnect means to the A/C unit. Secure the power "whip" to code. Call for re-inspection.

Miscellaneous/Other
Resolved
02/02/2022
Correction not made yet.

Miscellaneous/Other
Carried Forward
02/02/2022
Remove limited energy conductors from the power raceway "whip". Verify equipment grounding conductor installed at A/C whip.