PREL202110984
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Pending | |||
|
Corrections:
Miscellaneous/Other
Outstanding
02/02/2022
Remove limited energy conductors from the power raceway "whip".
Verify equipment grounding conductor installed at A/C whip.
|
||||
| Electrical Final Inspection | Failed | 9/7/2021 (10:00 - 12:00) | 9/7/2021 (AM) | 09/07/2021 |
|
Corrections:
Miscellaneous/Other
Carried Forward
09/07/2021
Remove limited energy conductors from the power raceway "whip".
Install equipment grounding conductor at the whip from disconnect means to the A/C unit.
Secure the power "whip" to code.
Call for re-inspection.
|
||||
| Electrical Final Inspection | Failed | 9/24/2021 (12:30 - 2:30) | 9/24/2021 (PM) | 09/24/2021 |
|
Corrections:
Miscellaneous/Other
Carried Forward
09/24/2021
Remove limited energy conductors from the power raceway "whip".
Install equipment grounding conductor at the whip from disconnect means to the A/C unit.
Secure the power "whip" to code.
Call for re-inspection.
|
||||
|
Miscellaneous/Other
Carried Forward
09/24/2021
Correction not made yet.
|
||||
| Electrical Final Inspection | Failed | 2/2/2022 (10:00 - 12:00) | 2/2/2022 (AM) | 02/02/2022 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/02/2022
Remove limited energy conductors from the power raceway "whip".
Install equipment grounding conductor at the whip from disconnect means to the A/C unit.
Secure the power "whip" to code.
Call for re-inspection.
|
||||
|
Miscellaneous/Other
Resolved
02/02/2022
Correction not made yet.
|
||||
|
Miscellaneous/Other
Carried Forward
02/02/2022
Remove limited energy conductors from the power raceway "whip".
Verify equipment grounding conductor installed at A/C whip.
|
||||