PREL202112662
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 10/5/2021 (2:30 - 3:30) | 10/5/2021 (PM) | 10/05/2021 |
Corrections:
Miscellaneous/Other
Comment Only
10/05/2021
RI for dining room area - ok
Change short section of 14-2 to 12-2 for the 20a circuit.
|
||||
Electrical Rough-in Inspection | Failed | 7/22/2022 (2:30 - 3:30) | 7/22/2022 (PM) | 07/25/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
07/25/2022
Install AFCI/ GFCI devices in small appliance circuits where homeruns enter kitchen on south wall.
|
||||
Miscellaneous/Other
Carried Forward
07/25/2022
Microwave receptacle installed on existing circuit on south wall, must have AFCI protection. GFCI protection required within 6' of sink.
|
||||
Miscellaneous/Other
Carried Forward
07/25/2022
Hood and gas range to be installed on same circuit with AFCI protection.
|
||||
Miscellaneous/Other
Carried Forward
07/25/2022
DW/ disposal circuit required to have AFCI/ GFCI protection at source.
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/27/2022 (12:30 - 2:30) | 7/27/2022 (PM) | 07/27/2022 |
Corrections:
Miscellaneous/Other
Resolved
07/27/2022
Install AFCI/ GFCI devices in small appliance circuits where homeruns enter kitchen on south wall.
|
||||
Miscellaneous/Other
Carried Forward
07/27/2022
Microwave receptacle installed on existing circuit on south wall, must have AFCI protection. GFCI protection required within 6' of sink.
|
||||
Miscellaneous/Other
Resolved
07/27/2022
Hood and gas range to be installed on same circuit with AFCI protection.
|
||||
Miscellaneous/Other
Resolved
07/27/2022
DW/ disposal circuit required to have AFCI/ GFCI protection at source.
|
||||
Miscellaneous/Other
Comment Only
07/27/2022
Corrections made for RI of west wall. Phase 1 of kitchen project- ok
|
||||
Electrical Rough-in Inspection | Partial Pass | 8/12/2022 (2:30 - 3:30) | 8/12/2022 (PM) | 08/12/2022 |
Corrections:
Miscellaneous/Other
Resolved
08/12/2022
Microwave receptacle installed on existing circuit on south wall, must have AFCI protection. GFCI protection required within 6' of sink.
|
||||
Miscellaneous/Other
Comment Only
08/12/2022
RI for south wall of kitchen- ok
|
||||
Electrical Rough-in Inspection | Passed | 9/29/2022 (2:30 - 3:30) | 9/29/2022 (PM) | 09/29/2022 |
Corrections:
Miscellaneous/Other
Comment Only
09/29/2022
Wall RI for kitchen - ok
|
||||
Electrical Final Inspection | Passed | 12/11/2023 (2:30 - 3:30) | 12/11/2023 (PM) | 12/11/2023 |
Corrections:
Miscellaneous/Other
Comment Only
12/11/2023
AFCI and GFCI- ok
|