PREL202112678
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 11/3/2021 (10:00 - 12:00) | 11/3/2021 (AM) | 11/03/2021 |
Corrections:
Miscellaneous/Other
Comment Only
11/03/2021
Phase 1
4 offices at south.
Misc - wall RI at conference room
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/30/2021 (10:00 - 12:00) | 11/30/2021 (AM) | 11/30/2021 |
Corrections:
Miscellaneous/Other
Comment Only
11/30/2021
RI- walls / RI OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/3/2022 (8:00 - 10:00) | 1/3/2022 (AM) | 01/03/2022 |
Corrections:
Miscellaneous/Other
Comment Only
01/03/2022
Hard lid and wall RI OK
|
||||
Electrical Rough-in Inspection | Not Ready | 3/2/2022 (12:30 - 2:30) | 3/2/2022 (PM) | 02/28/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
02/28/2022
Will reschedule
|
||||
Miscellaneous/Other
Carried Forward
02/28/2022
Will reschedule
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/24/2022 (8:00 - 10:00) | 3/24/2022 (AM) | 03/24/2022 |
Corrections:
Miscellaneous/Other
Resolved
03/24/2022
Will reschedule
|
||||
Miscellaneous/Other
Resolved
03/24/2022
Will reschedule
|
||||
Miscellaneous/Other
Comment Only
03/24/2022
Wall RI at coffee shop area
|
||||
Miscellaneous/Other
Carried Forward
03/24/2022
Preliminary review of additional service-
Verify with gear manufacturer for modification of side fed form bottom fed-
service conductors requiring separation and barriers as required in 230.62 ( C ).
Verify/ document and label available fault current
|
||||
Electrical Rough-in Inspection | Partial Pass | 5/9/2022 (8:00 - 10:00) | 5/9/2022 (AM) | 05/09/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
05/09/2022
Preliminary review of additional service-
Verify with gear manufacturer for modification of side fed form bottom fed-
service conductors requiring separation and barriers as required in 230.62 ( C ).
Verify/ document and label available fault current
|
||||
Miscellaneous/Other
Comment Only
05/09/2022
Ceiling ri phase l
|
||||
Electrical Rough-in Inspection | Partial Pass | 6/29/2022 (8:00 - 10:00) | 6/29/2022 (AM) | 06/30/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
06/30/2022
Preliminary review of additional service-
Verify with gear manufacturer for modification of side fed form bottom fed-
service conductors requiring separation and barriers as required in 230.62 ( C ).
Verify/ document and label available fault current
|
||||
Miscellaneous/Other
Comment Only
06/30/2022
Service meters released to Xcel for install.
Wall RI by loading dock area- ok
|
||||
Electrical Final Inspection | Partial Pass | 7/15/2022 (8:00 - 10:00) | 7/15/2022 (AM) | 07/15/2022 |
Corrections:
Miscellaneous/Other
Comment Only
07/15/2022
Final for office area- ok
|
||||
Miscellaneous/Other
Carried Forward
07/15/2022
Playground area needs GFCI for bath and drinking fountain
|
||||
Electrical Rough-in Inspection | Failed | 8/23/2022 (12:30 - 2:30) | 8/23/2022 (PM) | 08/23/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
08/23/2022
Preliminary review of additional service-
Verify with gear manufacturer for modification of side fed form bottom fed-
service conductors requiring separation and barriers as required in 230.62 ( C ).
Verify/ document and label available fault current
|
||||
Miscellaneous/Other
Carried Forward
08/23/2022
Above inspection for kitchen area and party room area. Kitchen area partially covered no above ceiling inspection, tile to be removed for viewing.
Ceilings in party room area, have cords installed above ceiling that are not allowed.
Fire Alarm wiring still needs above ceiling inspection for most areas before padding.
Lighting installed in party room area installed by low voltage contractor. This requires electrical permit and inspection.
No padding or finals in these areas before all inspections and proper permits are obtained and completed.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/6/2022 (Afternoon) | 9/6/2022 (PM) | 09/07/2022 |
Corrections:
Miscellaneous/Other
Resolved
09/07/2022
Preliminary review of additional service-
Verify with gear manufacturer for modification of side fed form bottom fed-
service conductors requiring separation and barriers as required in 230.62 ( C ).
Verify/ document and label available fault current
|
||||
Miscellaneous/Other
Carried Forward
09/07/2022
Panels and HVAC units require available fault current labeling.
Ceilings in party room area, have cords installed above ceiling that are not allowed.
Fire Alarm wiring still needs above ceiling inspection for most areas before padding.
Lighting installed in party room area installed by low voltage contractor. This requires electrical permit and inspection.
No padding or finals in these areas before all inspections and proper permits are obtained and completed.
|
||||
Miscellaneous/Other
Comment Only
09/07/2022
Kitchen ceiling- ok
No padding till all inspections are completed.
|
||||
Electrical Final Inspection | Failed | 10/12/2022 (10:00 - 12:00) | 10/12/2022 (AM) | 10/13/2022 |
Corrections:
Miscellaneous/Other
Resolved
10/13/2022
Playground area needs GFCI for bath and drinking fountain
|
||||
Miscellaneous/Other
Comment Only
10/13/2022
Lobby area- ok
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Complete wiring to parking lot lighting front of building.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Incomplete equipment wiring in dining area.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Coffee area requires GFCI for 208v receptacle on countertop.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Cappuccino machine in coffee area missing NRTL equipment listing.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Non permitted work for installation of coffee pot installed on counter.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Kitchen area requires CB locks for permanently wired equipment.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Missing CB blank in panel.
All new panels/ HVAC equipment require available fault current labeling. Equipment must be properly rated.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Walk in cooler and freezer condenser feeds reversed for CB and feeder sizes.
|
||||
Electrical Final Inspection | Failed | 10/13/2022 | ||
Corrections:
Miscellaneous/Other
Carried Forward
10/13/2022
Complete wiring to parking lot lighting front of building.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Incomplete equipment wiring in dining area.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Coffee area requires GFCI for 208v receptacle on countertop.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Cappuccino machine in coffee area missing NRTL equipment listing.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Non permitted work for installation of coffee pot installed on counter.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Kitchen area requires CB locks for permanently wired equipment.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Missing CB blank in panel.
All new panels/ HVAC equipment require available fault current labeling. Equipment must be properly rated.
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Walk in cooler and freezer condenser feeds reversed for CB and feeder sizes.
|
||||
Miscellaneous/Other
Comment Only
10/13/2022
Lobby area - ok
|
||||
Miscellaneous/Other
Carried Forward
10/13/2022
Low Voltage lighting in ballroom area may require some additional wiring to correct power supply issue. Work can be performed under this permit or an additional permit would be required if closed beforehand.
|
||||
Electrical Final Inspection | Partial Pass | 10/26/2022 (8:00 - 10:00) | 10/26/2022 (AM) | 10/27/2022 |
Corrections:
Miscellaneous/Other
Resolved
10/27/2022
Complete wiring to parking lot lighting front of building.
|
||||
Miscellaneous/Other
Resolved
10/27/2022
Incomplete equipment wiring in dining area.
|
||||
Miscellaneous/Other
Resolved
10/27/2022
Coffee area requires GFCI for 208v receptacle on countertop.
|
||||
Miscellaneous/Other
Resolved
10/27/2022
Cappuccino machine in coffee area missing NRTL equipment listing.
Unit is not listed and will be replaced per EH inspector and PM. This is a plug in unit, building wiring is ok.
|
||||
Miscellaneous/Other
Carried Forward
10/27/2022
Non permitted work for installation of coffee pot installed on counter.
|
||||
Miscellaneous/Other
Resolved
10/27/2022
Kitchen area requires CB locks for permanently wired equipment.
|
||||
Miscellaneous/Other
Carried Forward
10/27/2022
All new panels/ HVAC equipment require available fault current labeling. Equipment must be properly rated.
|
||||
Miscellaneous/Other
Resolved
10/27/2022
Walk in cooler and freezer condenser feeds reversed for CB and feeder sizes.
|
||||
Miscellaneous/Other
Carried Forward
10/27/2022
Low Voltage lighting in ballroom area may require some additional wiring to correct power supply issue. Work can be performed under this permit or an additional permit would be required if closed beforehand.
|
||||
Electrical Final Inspection | Passed | 11/1/2022 (10:00 - 12:00) | 11/1/2022 (AM) | 11/03/2022 |
Corrections:
Miscellaneous/Other
Resolved
11/03/2022
Non permitted work for installation of coffee pot installed on counter. Contractor reviewed work installation for compliance - ok
|
||||
Miscellaneous/Other
Resolved
11/03/2022
All new panels/ HVAC equipment require available fault current labeling. Equipment must be properly rated.
|
||||
Miscellaneous/Other
Resolved
11/03/2022
Low Voltage lighting in ballroom area may require some additional wiring to correct power supply issue. Work can be performed under this permit or an additional permit would be required if closed beforehand.
Contractor will not be involved in this work, if they are hired to complete a new permit will be pulled.
|
||||
Miscellaneous/Other
Comment Only
11/03/2022
Contractor completed work as originally hired to complete. Any work beyond this point of inspection will require new electrical permits.
New light fixtures were observed to be installed this work is not being completed by Manor electric. Nor is the work to complete the installation of new power supplies for low voltage lighting being covered under this permit.
Final ok for original work that was observed.
|