Permit Application Status

PREL202113244


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202113244
Electrical
Expired
ROERS MN OPP ZONE FUND LLC
Other
temp power; 400A 1PH 16 circuits
10/05/2021
10/07/2021
06/01/2022

Locations

Permits

Permit Number: PREL202113244

Electrical
Expired
10/07/2021
06/01/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
12/03/2021
OK to release to Xcel. Label available fault current at service

Electrical Final Inspection Failed 11/29/2021 (8:00 - 10:00) 11/29/2021 (AM) 11/29/2021
Corrections:


Miscellaneous/Other
Carried Forward
11/29/2021
1. Install main bond screw at 200 AMP service at panel east of meter enclosure. 2. Install second ground rod. 3. Service has a 10,000 AMP A.I.C. rating- provide label for available fault current- Xcel transformer is in place and size and length of service conductors is known. Call for re-inspection.

Electrical Final Inspection Partial Pass 12/2/2021 (10:00 - 12:00) 12/2/2021 (AM) 12/03/2021
Corrections:


Miscellaneous/Other
Resolved
12/03/2021
1. Install main bond screw at 200 AMP service at panel east of meter enclosure. 2. Install second ground rod. 3. Service has a 10,000 AMP A.I.C. rating- provide label for available fault current- Xcel transformer is in place and size and length of service conductors is known. Call for re-inspection.

Miscellaneous/Other
Carried Forward
12/03/2021
OK to release to Xcel. Label available fault current at service