PREL202114122
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Passed | 10/26/2021 (10:00 - 12:00) | 10/26/2021 (AM) | 10/26/2021 |
Electrical Final Inspection | Not Ready | 10/26/2021 (10:00 - 12:00) | 10/26/2021 (AM) | 10/26/2021 |
Corrections:
Miscellaneous/Other
Carried Forward
10/26/2021
Unlisted tool- lacks NRTL.
Requires independent 3rd party evaluation.
Installation work OK.
|
||||
Electrical Final Inspection | Partial Pass | 11/9/2021 (10:00 - 12:00) | 11/9/2021 (AM) | 11/09/2021 |
Corrections:
Miscellaneous/Other
Carried Forward
11/09/2021
Unlisted tool- lacks NRTL.
Requires independent 3rd party evaluation.
Installation work OK.
|
||||
Miscellaneous/Other
Carried Forward
11/09/2021
Additional inspection-
Provide secondary conductor overcurrent protection for transformer secondary conductors.
Provide connection to establish a ground electrical system with a intentionally grounded circuit conductor.
Call for subsequent field inspection.
|
||||
Electrical Final Inspection | Not Ready | 11/15/2021 (10:00 - 12:00) | 11/15/2021 (AM) | 11/15/2021 |
Corrections:
Miscellaneous/Other
Carried Forward
11/15/2021
Unlisted tool- lacks NRTL.
Requires independent 3rd party evaluation.
Installation work OK.
|
||||
Miscellaneous/Other
Carried Forward
11/15/2021
Additional inspection-
Provide secondary conductor overcurrent protection for transformer secondary conductors.
Provide connection to establish a ground electrical system with a intentionally grounded circuit conductor.
Call for subsequent field inspection.
|
||||
Miscellaneous/Other
Comment Only
11/15/2021
Contact had scheduling conflict- Please reschedule
|
||||
Electrical Final Inspection | Partial Pass | 11/23/2021 (10:00 - 12:00) | 11/23/2021 (AM) | 11/23/2021 |
Corrections:
Miscellaneous/Other
Resolved
02/25/2022
Unlisted tool- lacks NRTL.
Requires independent 3rd party evaluation.
Installation work OK.
|
||||
Miscellaneous/Other
Resolved
02/25/2022
Additional inspection-
Provide secondary conductor overcurrent protection for transformer secondary conductors.
Provide connection to establish a ground electrical system with a intentionally grounded circuit conductor.
Call for subsequent field inspection.
|
||||
Miscellaneous/Other
Resolved
02/25/2022
Final OK pending 3rd party evaluation.
|
||||
Electrical Final Inspection | Passed | 02/25/2022 | ||
Corrections:
Miscellaneous/Other
Outstanding
11/23/2021
Final OK pending 3rd party evaluation.
|