Summary

PREL202116039
Electrical
Finaled
;
PETERS PROPERTIES II LLC
Alteration/Repair/Replace
Install (1) 400-amp feeder, (1) 300kva transformer, (1) 600-amp feeder, (3) 150 feeds to PDUs and install branch circuit wiring for mechanical equipment. Project 220050
12/07/2021
12/08/2021
06/05/2023
12/07/2022

Locations

Permits

Permit Number: PREL202116039

Electrical
Finaled
12/08/2021
06/05/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 8/17/2022 (10:00 - 12:00) 8/17/2022 (AM) 08/17/2022
See corrections
Corrections:


Miscellaneous/Other
Carried Forward
08/17/2022
Will have fault currents available at the final 110.24. Will relocate disconnect on outside equipment for working clearances.

Electrical Final Inspection Passed 12/7/2022 (12:30 - 2:30) 12/7/2022 (PM) 12/07/2022
12/6/22 inspection cancelled and contractor will call to reschedule. [jsmidt @ 12/05/2022 10:45 AM] Corrections all fixed. Labeled the fault current and moved the outside disconnects.
Corrections:


Miscellaneous/Other
Comment Only
12/07/2022
Finaled permit for equipment that is being moved to Canada now and taking everything with the large containers.