Summary

PREL202200658
Electrical
Finaled
OXBOW REALTY PARTNERS LLC
Alteration/Repair/Replace
install and Connect owners electrical equipment for N2 plant at SkyWater Technology.
01/20/2022
02/17/2022
01/01/2024
07/05/2023

Locations

Permits

Permit Number: PREL202200658

Electrical
Finaled
02/17/2022
01/01/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Failed 2/22/2022 (8:00 - 10:00) 2/22/2022 (AM) 02/22/2022
Corrections:


Miscellaneous/Other
Comment Only
02/22/2022
Meeting at site- to discuss equipment installations and NRTL listing and labeling

All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified
Carried Forward
02/22/2022
All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified. The equipment structure lacks any nameplate and has no nationally recognized label or nomenclature. There are multiple issues: There is premise wiring within and on the structure- factory wiring for lights, receptacle outlets, panelboards - this wiring is complete and totally installed- as such such work is subject to either: field inspection per NEC requirements- such work would require a separate electrical permit/ have the electrical contractor disassemble any completed installations/review & correct if necessary & call for electrical inspection. Or such work is subject to independent 3rd party evaluations by P.E. per MN Electrical Act rules. The electrical equipment/ electrical apparatus/ industrial control panels - wiring ( regardless of voltage ) and industrial machines contained within or on the structure are not NRTL labeled. There is a Industrial Control Panel - installed in this structure with a U.L. listing label- photos of labeling were provided by inspector to UL Senior Regulatory Engineer- The Engineer response is that UL does not recognize the labels as being their "mark"- that such labeling is not certified by the testing lab. As such- until such time as can be determined otherwise- such equipment is considered as unlisted/unlabeled. Such equipment requires independent 3rd party PE evaluation.

Miscellaneous/Other
Carried Forward
02/22/2022
There is no approval labeling for the 4160 volt motor - Inspector is waiting for the electrical engineer of record and and other parties to review and evaluate this equipment- make recommendations for acceptance Until such review and approval is made- this equipment may not be energized.

Miscellaneous/Other
Carried Forward
02/22/2022
To date- no electrical plan set has been submitted for review by the jurisdiction. Such plans require MN State Licensed PE / or Master of Record review/sign and stamp.

Miscellaneous/Other
Carried Forward
02/22/2022
There is a piece of equipment ( machine ) that has a ETL ( NRTL ) listing mark. This label covers only the industrial control panel and not any of the wiring or equipment installed in or on the machine ( skid ). Any unlisted equipment requires independent 3rd party PE review and evaluation per MN Electrical Act rules. This is for the "machine" or apparatus in its entirety - electrically.

Miscellaneous/Other
Carried Forward
02/22/2022
There is an industrial control panel mounted at the exterior- This equipment bears a UL mark- per UL Senior Regulatory Engineer- based on photos provided by the AHJ- UL does not recognize this label as being their approval label. Until such labeling is reconciled- this equipment is considered unlisted. Unlisted equipment requires Independent 3rd party evaluation per MN Electrical Act rules.

Miscellaneous/Other
Carried Forward
02/22/2022
The list of potentially unlisted equipment may not be complete- any or all electrical equipment/machine/apparatus and wiring ( regardless of voltage ) to, in or on such skids, platforms/equipment sheds or the like require independent 3rd party evaluation- as outlined in this report.

Electrical Rough-in Inspection Partial Pass 2/23/2022 2/23/2022 (AM) 02/25/2022
Corrections:


Miscellaneous/Other
Comment Only
02/25/2022
Site visit-progress inspection

Electrical Rough-in Inspection Partial Pass 2/24/2022 (8:00 - 10:00) 2/24/2022 (AM) 02/25/2022
Corrections:


Miscellaneous/Other
Comment Only
02/25/2022
Progress inspection

Electrical Rough-in Inspection Partial Pass 2/25/2022 (12:30 - 2:30) 2/25/2022 (PM) 02/25/2022
Corrections:


All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified
Carried Forward
02/25/2022
All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified. The equipment structure lacks any nameplate and has no nationally recognized label or nomenclature. There are multiple issues: There is premise wiring within and on the structure- factory wiring for lights, receptacle outlets, panelboards - this wiring is complete and totally installed- as such such work is subject to either: field inspection per NEC requirements- such work would require a separate electrical permit/ have the electrical contractor disassemble any completed installations/review & correct if necessary & call for electrical inspection. Or such work is subject to independent 3rd party evaluations by P.E. per MN Electrical Act rules. The electrical equipment/ electrical apparatus/ industrial control panels - wiring ( regardless of voltage ) and industrial machines contained within or on the structure are not NRTL labeled. There is a Industrial Control Panel - installed in this structure with a U.L. listing label- photos of labeling were provided by inspector to UL Senior Regulatory Engineer- The Engineer response is that UL does not recognize the labels as being their "mark"- that such labeling is not certified by the testing lab. As such- until such time as can be determined otherwise- such equipment is considered as unlisted/unlabeled. Such equipment requires independent 3rd party PE evaluation.

Miscellaneous/Other
Carried Forward
02/25/2022
There is no approval labeling for the 4160 volt motor - Inspector is waiting for the electrical engineer of record and and other parties to review and evaluate this equipment- make recommendations for acceptance Until such review and approval is made- this equipment may not be energized.

Miscellaneous/Other
Carried Forward
02/25/2022
To date- no electrical plan set has been submitted for review by the jurisdiction. Such plans require MN State Licensed PE / or Master of Record review/sign and stamp.

Miscellaneous/Other
Carried Forward
02/25/2022
There is a piece of equipment ( machine ) that has a ETL ( NRTL ) listing mark. This label covers only the industrial control panel and not any of the wiring or equipment installed in or on the machine ( skid ). Any unlisted equipment requires independent 3rd party PE review and evaluation per MN Electrical Act rules. This is for the "machine" or apparatus in its entirety - electrically.

Miscellaneous/Other
Carried Forward
02/25/2022
There is an industrial control panel mounted at the exterior- This equipment bears a UL mark- per UL Senior Regulatory Engineer- based on photos provided by the AHJ- UL does not recognize this label as being their approval label. Until such labeling is reconciled- this equipment is considered unlisted. Unlisted equipment requires Independent 3rd party evaluation per MN Electrical Act rules.

Miscellaneous/Other
Carried Forward
02/25/2022
The list of potentially unlisted equipment may not be complete- any or all electrical equipment/machine/apparatus and wiring ( regardless of voltage ) to, in or on such skids, platforms/equipment sheds or the like require independent 3rd party evaluation- as outlined in this report.

Miscellaneous/Other
Carried Forward
02/25/2022
progress inspection

Electrical Rough-in Inspection Partial Pass 3/4/2022 (7:00 - 8:00) 3/4/2022 (AM) 03/04/2022
Corrections:


All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified
Carried Forward
03/04/2022
All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified. The equipment structure lacks any nameplate and has no nationally recognized label or nomenclature. There are multiple issues: There is premise wiring within and on the structure- factory wiring for lights, receptacle outlets, panelboards - this wiring is complete and totally installed- as such such work is subject to either: field inspection per NEC requirements- such work would require a separate electrical permit/ have the electrical contractor disassemble any completed installations/review & correct if necessary & call for electrical inspection. Or such work is subject to independent 3rd party evaluations by P.E. per MN Electrical Act rules. The electrical equipment/ electrical apparatus/ industrial control panels - wiring ( regardless of voltage ) and industrial machines contained within or on the structure are not NRTL labeled. There is a Industrial Control Panel - installed in this structure with a U.L. listing label- photos of labeling were provided by inspector to UL Senior Regulatory Engineer- The Engineer response is that UL does not recognize the labels as being their "mark"- that such labeling is not certified by the testing lab. As such- until such time as can be determined otherwise- such equipment is considered as unlisted/unlabeled. Such equipment requires independent 3rd party PE evaluation.

Miscellaneous/Other
Carried Forward
03/04/2022
There is no approval labeling for the 4160 volt motor - Inspector is waiting for the electrical engineer of record and and other parties to review and evaluate this equipment- make recommendations for acceptance Until such review and approval is made- this equipment may not be energized.

Miscellaneous/Other
Carried Forward
03/04/2022
To date- no electrical plan set has been submitted for review by the jurisdiction. Such plans require MN State Licensed PE / or Master of Record review/sign and stamp.

Miscellaneous/Other
Carried Forward
03/04/2022
There is a piece of equipment ( machine ) that has a ETL ( NRTL ) listing mark. This label covers only the industrial control panel and not any of the wiring or equipment installed in or on the machine ( skid ). Any unlisted equipment requires independent 3rd party PE review and evaluation per MN Electrical Act rules. This is for the "machine" or apparatus in its entirety - electrically.

Miscellaneous/Other
Carried Forward
03/04/2022
There is an industrial control panel mounted at the exterior- This equipment bears a UL mark- per UL Senior Regulatory Engineer- based on photos provided by the AHJ- UL does not recognize this label as being their approval label. Until such labeling is reconciled- this equipment is considered unlisted. Unlisted equipment requires Independent 3rd party evaluation per MN Electrical Act rules.

Miscellaneous/Other
Carried Forward
03/04/2022
The list of potentially unlisted equipment may not be complete- any or all electrical equipment/machine/apparatus and wiring ( regardless of voltage ) to, in or on such skids, platforms/equipment sheds or the like require independent 3rd party evaluation- as outlined in this report.

Miscellaneous/Other
Carried Forward
03/04/2022
progress inspection

Miscellaneous/Other
Carried Forward
03/04/2022
4160 testing reports shall be emailed to AHJ from either Preferred electric and/or Hunt electric. Ok to energize.

Electrical Rough-in Inspection Passed 04/26/2022
Corrections:


All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified
Outstanding
03/04/2022
All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified. The equipment structure lacks any nameplate and has no nationally recognized label or nomenclature. There are multiple issues: There is premise wiring within and on the structure- factory wiring for lights, receptacle outlets, panelboards - this wiring is complete and totally installed- as such such work is subject to either: field inspection per NEC requirements- such work would require a separate electrical permit/ have the electrical contractor disassemble any completed installations/review & correct if necessary & call for electrical inspection. Or such work is subject to independent 3rd party evaluations by P.E. per MN Electrical Act rules. The electrical equipment/ electrical apparatus/ industrial control panels - wiring ( regardless of voltage ) and industrial machines contained within or on the structure are not NRTL labeled. There is a Industrial Control Panel - installed in this structure with a U.L. listing label- photos of labeling were provided by inspector to UL Senior Regulatory Engineer- The Engineer response is that UL does not recognize the labels as being their "mark"- that such labeling is not certified by the testing lab. As such- until such time as can be determined otherwise- such equipment is considered as unlisted/unlabeled. Such equipment requires independent 3rd party PE evaluation.

Miscellaneous/Other
Outstanding
03/04/2022
There is no approval labeling for the 4160 volt motor - Inspector is waiting for the electrical engineer of record and and other parties to review and evaluate this equipment- make recommendations for acceptance Until such review and approval is made- this equipment may not be energized.

Miscellaneous/Other
Outstanding
03/04/2022
To date- no electrical plan set has been submitted for review by the jurisdiction. Such plans require MN State Licensed PE / or Master of Record review/sign and stamp.

Miscellaneous/Other
Outstanding
03/04/2022
There is a piece of equipment ( machine ) that has a ETL ( NRTL ) listing mark. This label covers only the industrial control panel and not any of the wiring or equipment installed in or on the machine ( skid ). Any unlisted equipment requires independent 3rd party PE review and evaluation per MN Electrical Act rules. This is for the "machine" or apparatus in its entirety - electrically.

Miscellaneous/Other
Outstanding
03/04/2022
There is an industrial control panel mounted at the exterior- This equipment bears a UL mark- per UL Senior Regulatory Engineer- based on photos provided by the AHJ- UL does not recognize this label as being their approval label. Until such labeling is reconciled- this equipment is considered unlisted. Unlisted equipment requires Independent 3rd party evaluation per MN Electrical Act rules.

Miscellaneous/Other
Outstanding
03/04/2022
The list of potentially unlisted equipment may not be complete- any or all electrical equipment/machine/apparatus and wiring ( regardless of voltage ) to, in or on such skids, platforms/equipment sheds or the like require independent 3rd party evaluation- as outlined in this report.

Miscellaneous/Other
Outstanding
03/04/2022
progress inspection

Miscellaneous/Other
Outstanding
03/04/2022
4160 testing reports shall be emailed to AHJ from either Preferred electric and/or Hunt electric. Ok to energize.

Electrical Final Inspection Partial Pass 04/26/2022
Corrections:


Miscellaneous/Other
Comment Only
04/26/2022
Independent 3rd party evaluations received.

Electrical Final Inspection Passed 7/5/2023 (8:00 - 10:00) 7/5/2023 (AM) 07/05/2023
Corrections:


Miscellaneous/Other
Comment Only
07/05/2023
Missing information has been reviewed and filed with building owner.