PREL202201556
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Passed | 6/17/2022 (10:00 - 12:00) | 6/17/2022 (AM) | 06/17/2022 |
Corrections:
Miscellaneous/Other
Comment Only
06/17/2022
RI completed.
|
||||
Electrical Final Inspection | Failed | 6/17/2022 (10:00 - 12:00) | 6/17/2022 (AM) | 06/22/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
06/22/2022
Bonding jumper and GEC sizing required to be minimum #2
|
||||
Miscellaneous/Other
Carried Forward
06/22/2022
LED power supplies have component listing not an approved NRTL listing.
Power supplies above ceiling having flexible cords. Cannot be above ceiling 400.12
|
||||
Miscellaneous/Other
Carried Forward
06/22/2022
Automatic lighting in room with electrical equipment required to be manual. 110.26D
|
||||
Miscellaneous/Other
Carried Forward
06/22/2022
Available fault current labeling required for new panels.
|
||||
Electrical Final Inspection | Passed | 7/7/2022 (10:00 - 12:00) | 7/7/2022 (AM) | 07/08/2022 |
Corrections:
Miscellaneous/Other
Resolved
07/08/2022
Bonding jumper and GEC sizing required to be minimum #2
|
||||
Miscellaneous/Other
Resolved
07/08/2022
LED power supplies have component listing not an approved NRTL listing.
Power supplies above ceiling having flexible cords. Cannot be above ceiling 400.12
|
||||
Miscellaneous/Other
Resolved
07/08/2022
Automatic lighting in room with electrical equipment required to be manual. 110.26D
|
||||
Miscellaneous/Other
Resolved
07/08/2022
Available fault current labeling required for new panels.
|