Summary

PREL202202572
Electrical
Finaled
AEON VP BLOOMINGTON 172 LIMITED PARTNERSHIP
Other
Installing a 51.2 kW DC/ 37.8 kW AC PV solar system on the apartment building roof
03/15/2022
03/25/2022
05/15/2023
11/16/2022

Locations

Permits

Permit Number: PREL202202572

Electrical
Finaled
03/25/2022
05/15/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Failed 10/27/2022 (2:30 - 3:30) 10/27/2022 (PM) 10/28/2022
Corrections:


Miscellaneous/Other
Carried Forward
10/28/2022
Available fault currents needed. Labeling required on service and all OCP enclosures.

Miscellaneous/Other
Carried Forward
10/28/2022
Feeder wiring on roof required to be properly supported and not laying on roof.

Miscellaneous/Other
Carried Forward
10/28/2022
Seal tight used to protect PV wiring required to be properly bonded around to array racking. Seal tights required to be properly supported.

Miscellaneous/Other
Carried Forward
10/28/2022
PV wiring required to be properly supported at a minimum per NEC 690.31C1

Electrical Final Inspection Passed 11/16/2022 (10:00 - 12:00) 11/16/2022 (AM) 11/16/2022
Corrections:


Miscellaneous/Other
Resolved
11/16/2022
Available fault currents needed. Labeling required on service and all OCP enclosures.

Miscellaneous/Other
Resolved
11/16/2022
Feeder wiring on roof required to be properly supported and not laying on roof.

Miscellaneous/Other
Resolved
11/16/2022
Seal tight used to protect PV wiring required to be properly bonded around to array racking. Seal tights required to be properly supported.

Miscellaneous/Other
Resolved
11/16/2022
PV wiring required to be properly supported at a minimum per NEC 690.31C1