PREL202203500
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 5/27/2022 (10:00 - 12:00) | 5/27/2022 (AM) | 05/27/2022 |
Corrections:
Miscellaneous/Other
Comment Only
05/27/2022
Outside wall ri
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/29/2022 (10:00 - 12:00) | 7/29/2022 (AM) | 07/29/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
07/29/2022
Pantry and two bathroom wall and ceiling ri
|
||||
Electrical Rough-in Inspection | Passed | 8/4/2022 (2:30 - 3:30) | 8/4/2022 (PM) | 08/04/2022 |
Corrections:
Miscellaneous/Other
Outstanding
07/29/2022
Pantry and two bathroom wall and ceiling ri
|
||||
Miscellaneous/Other
Comment Only
08/04/2022
Disco room ri
|
||||
Electrical Rough-in Inspection | Passed | 1/13/2023 (12:30 - 2:30) | 1/13/2023 (PM) | 01/13/2023 |
Corrections:
Miscellaneous/Other
Comment Only
01/13/2023
Service inspection ok
Back door is unlocked- called John my contact to inform him of that- I did not unlock door
|
||||
Electrical Final Inspection | Failed | 3/2/2023 (12:30 - 2:30) | 3/2/2023 (PM) | 03/02/2023 |
Corrections:
Miscellaneous/Other
Carried Forward
03/02/2023
Drinking fountain needs GFI protection
Dryer receptacle needs GFI protection
All receptacles need to be tamper resistant type
All disco lights on ceiling are not listed
All disco lights on walls are not listed
LED drivers in cabinets are not listed and are class l drivers with class ll wiring
Disco room lights have cords going through ceiling , receptacles need to be below ceiling
|
||||
Electrical Final Inspection | Passed | 3/13/2023 (8:00 - 10:00) | 3/13/2023 (AM) | 03/13/2023 |
Corrections:
Miscellaneous/Other
Outstanding
03/02/2023
Drinking fountain needs GFI protection
Dryer receptacle needs GFI protection
All receptacles need to be tamper resistant type
All disco lights on ceiling are not listed
All disco lights on walls are not listed
LED drivers in cabinets are not listed and are class l drivers with class ll wiring
Disco room lights have cords going through ceiling , receptacles need to be below ceiling
|
||||
Miscellaneous/Other
Comment Only
03/13/2023
All unlisted lights removed
Proper drivers installed
GFI breakers ok
|
||||
Lighting Inspection Sign | Passed | 3/13/2023 (8:00 - 10:00) | 3/13/2023 (AM) | 03/24/2023 |
KIDS EMPIRE |