PREL202206296
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Pending | |||
Corrections:
Miscellaneous/Other
Outstanding
07/08/2022
Listed power supplies for sign need to be installed.
|
||||
Miscellaneous/Other
Outstanding
07/08/2022
CB locks for EM lighting need to be installed
Schedule reinspection when ready.
|
||||
Electrical Rough-in Inspection | Partial Pass | 6/8/2022 (8:00 - 10:00) | 6/8/2022 (AM) | 06/08/2022 |
Corrections:
Miscellaneous/Other
Comment Only
06/08/2022
Wall RI- ok
|
||||
Electrical Rough-in Inspection | Passed | 7/7/2022 (2:30 - 3:30) | 7/7/2022 (PM) | 07/08/2022 |
Electrical Final Inspection | Failed | 7/7/2022 (2:30 - 3:30) | 7/7/2022 (PM) | 07/08/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
07/08/2022
Listed power supplies for sign need to be installed.
|
||||
Miscellaneous/Other
Carried Forward
07/08/2022
CB locks for EM lighting need to be installed
Schedule reinspection when ready.
|
||||
Electrical Final Inspection | Passed | 7/11/2022 (8:00 - 10:00) | 7/11/2022 (AM) | 07/11/2022 |
Fixed corrections- Ok now. | ||||
Corrections:
Miscellaneous/Other
Comment Only
07/11/2022
Fixed listed power supplies for front sign.
Put on lock out on breaker for exit emergency circuit.
|