Permit Application Status

PREL202208850


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202208850
Electrical
Finaled
AEON VP BLOOMINGTON LLC
Other
Install new electric service for EV charging. 120/208 400amp outdoor service.
07/20/2022
07/22/2022
07/23/2023
01/24/2023

Locations

Permits

Permit Number: PREL202208850

Electrical
Finaled
07/22/2022
07/23/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Passed 8/16/2022 (8:00 - 10:00) 8/16/2022 (AM) 08/16/2022
Corrections:


Miscellaneous/Other
Comment Only
08/16/2022
UG only- ok

Electrical Final Inspection Failed 1/17/2023 (8:00 - 10:00) 1/17/2023 (AM) 01/18/2023
Corrections:


Miscellaneous/Other
Carried Forward
01/18/2023
SCCR rating of equipment does not meet the minimum available fault listed on service.

Electrical Final Inspection Passed 1/23/2023 (12:30 - 2:30) 1/23/2023 (PM) 01/24/2023
Corrections:


Miscellaneous/Other
Resolved
01/24/2023
SCCR rating of equipment does not meet the minimum available fault listed on service.

Miscellaneous/Other
Comment Only
01/24/2023
Service equipment swapped out with properly rated equipment. Xcel contacted for connection.