PREL202211680
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 10/6/2022 (10:00 - 12:00) | 10/6/2022 (AM) | 10/06/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
10/06/2022
Ceiling and wall area - ok
No soffits with speaker cabling laying on them not properly supported.
|
||||
Electrical Final Inspection | Partial Pass | 10/28/2022 (10:00 - 12:00) | 10/28/2022 (AM) | 10/28/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
10/28/2022
Store front sign has listing issues. Sign has multiple listing marks that do not match proper NRTL listing marks.
|
||||
Miscellaneous/Other
Carried Forward
10/28/2022
Information needed on lighted displays. NRTL listing information needed for powered displays with lighting.
|
||||
Miscellaneous/Other
Comment Only
10/28/2022
Temp. opening -ok
|
||||
Electrical Final Inspection | Passed | 11/18/2022 | ||
Corrections:
Miscellaneous/Other
Resolved
11/18/2022
Store front sign has listing issues. Sign has multiple listing marks that do not match proper NRTL listing marks.
|
||||
Miscellaneous/Other
Resolved
11/18/2022
Information needed on lighted displays. NRTL listing information needed for powered displays with lighting.
|
||||
Miscellaneous/Other
Comment Only
11/18/2022
Issues resolved, sign listing ok removal of old stickers required.
Display evaluation attached to permit from PE for future reference.
|