Summary

PREL202212684
Electrical
Finaled
PWS HOLDINGS 19 LLC
Other
Ground up car wash- electrical.
10/06/2022
01/04/2023
05/28/2024

Locations

Permits

Permit Number: PREL202212684

Electrical
Finaled
01/04/2023
05/28/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 4/6/2023 (8:00 - 10:00) 4/6/2023 (AM) 04/06/2023
Corrections:


Miscellaneous/Other
Comment Only
04/06/2023
R. I. Ufer ground for car wash.

Electrical Rough-in Inspection Partial Pass 5/18/2023 (10:00 - 12:00) 5/18/2023 (AM) 05/18/2023
Corrections:


Miscellaneous/Other
Comment Only
05/18/2023
R. I. Underground PVC conduits under the slabs in the building.

Electrical Rough-in Inspection Partial Pass 5/23/2023 (8:00 - 10:00) 5/23/2023 (AM) 05/23/2023
Corrections:


Miscellaneous/Other
Comment Only
05/23/2023
R. I. Underground interior of the building for for vacuum stations and other equipment.

Electrical Rough-in Inspection Partial Pass 7/20/2023 (10:00 - 12:00) 7/20/2023 (AM) 07/20/2023
Corrections:


Miscellaneous/Other
Comment Only
07/20/2023
UG for parking area and service pipes- ok

Electrical Rough-in Inspection Partial Pass 7/21/2023 (12:30 - 2:30) 7/21/2023 (PM) 07/21/2023
Corrections:


Miscellaneous/Other
Comment Only
07/21/2023
UG

Electrical Rough-in Inspection Partial Pass 8/17/2023 (8:00 - 10:00) 8/17/2023 (AM) 08/17/2023
Corrections:


Miscellaneous/Other
Comment Only
08/17/2023
R. I. Underground light base poles.

Electrical Rough-in Inspection Partial Pass 9/6/2023 (12:30 - 2:30) 9/6/2023 (PM) 09/06/2023
Corrections:


Miscellaneous/Other
Comment Only
09/06/2023
R. I. Interior walls of the car wash only.

Electrical Rough-in Inspection Failed 9/29/2023 (10:00 - 12:00) 9/29/2023 (AM) 09/29/2023
Corrections:


Miscellaneous/Other
Carried Forward
09/29/2023
Service missing main bonding jumper. CT cabinet missing bonding jumper. GEC needs to be connected to building steel. Water bonding connection not complete.

Electrical Rough-in Inspection Partial Pass 10/2/2023 (12:30 - 2:30) 10/2/2023 (PM) 10/02/2023
Service-Ok
Corrections:


Miscellaneous/Other
Resolved
10/02/2023
Service missing main bonding jumper. CT cabinet missing bonding jumper. GEC needs to be connected to building steel. Water bonding connection not complete.

Miscellaneous/Other
Comment Only
10/02/2023
Notified Xcel Energy for 800 amp service inspection-Ok

Lighting Inspection Passed 10/24/2023
Electrical Rough-in Inspection Passed 11/28/2023 (8:00 - 10:00) 11/28/2023 (AM) 11/28/2023
Corrections:


Miscellaneous/Other
Comment Only
11/28/2023
R. I. Ceilings- Bathrooms and control room.

Electrical Final Inspection Passed 11/30/2023 (10:00 - 12:00) 11/30/2023 (AM) 11/30/2023