temp power; 1-400A 1PH 16 circuits, 1-200A 1PH 8 circuits
10/29/2022
10/31/2022
05/30/2023

Locations

Permits

Permit Number: PREL202213652

Electrical
Expired
10/31/2022
05/30/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
12/01/2022
GEC on 200a service needs to be connected to Neutral bar. The frame of the trailer required to be bonded to a Grounding electrode. Available fault currents will be required to be labeled when service connections completed.

Electrical Final Inspection Partial Pass 12/1/2022 (10:00 - 12:00) 12/1/2022 (AM) 12/01/2022
Corrections:


Miscellaneous/Other
Carried Forward
12/01/2022
GEC on 200a service needs to be connected to Neutral bar. The frame of the trailer required to be bonded to a Grounding electrode. Available fault currents will be required to be labeled when service connections completed.

Miscellaneous/Other
Comment Only
12/01/2022
Services released to Xcel for connection.