Summary

PREL202214293
Electrical
Finaled
OXBOW REALTY PARTNERS LLC
Alteration/Repair/Replace
9400 Additions: (2241.4683) 1. Install 70’ of 1-1/4” EMT from 208V panel for 100A 3-P breaker. a. Energized work permit required 2. Install 50’ of 3/4” EMT from 208v panel for two 3phase breakers for trillium pumps a. The lock load pump requires a 20a breaker b. The process pump requires a 30a breaker c. All pumps will have twist lock disconnect 3. Install 50’ pipe For 2 floor boxes around tool in fab for general purpose receptacles 4. The heat trace is roughly 300’. a. Heat Trace provided by others b. Time to install heat trace will be extensive due to amount of existing process piping. 5. Scrubber - 60’ EMT for 60a 208v breaker a. Twist Lock Pin and Sleeve required for Quick Disconnect
11/14/2022
11/14/2022
06/19/2023
12/21/2022

Locations

Permits

Permit Number: PREL202214293

Electrical
Finaled
11/14/2022
06/19/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Partial Pass 11/21/2022 (12:30 - 2:30) 11/21/2022 (PM) 11/21/2022
Corrections:


Miscellaneous/Other
Carried Forward
11/21/2022
NRTL evaluation required for equipment (Tool) installed in fab area .

Miscellaneous/Other
Comment Only
11/21/2022
Wiring to units -OK

Electrical Final Inspection Passed 12/21/2022
Corrections:


Miscellaneous/Other
Resolved
12/21/2022
NRTL evaluation required for equipment (Tool) installed in fab area .

Miscellaneous/Other
Comment Only
12/21/2022
Evaluation received and attached to permit- ok