PREL202214826
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 12/21/2022 (8:00 - 10:00) | 12/21/2022 (AM) | 12/21/2022 |
Corrections:
Miscellaneous/Other
Comment Only
12/21/2022
Partial wall RI - ok
|
||||
Electrical Rough-in Inspection | Failed | 3/29/2024 (10:00 - 12:00) | 3/29/2024 (AM) | 04/01/2024 |
Corrections:
Miscellaneous/Other
Carried Forward
04/01/2024
GEC required to be bonded to can of services.
Tighten all connections.
|
||||
Miscellaneous/Other
Carried Forward
04/01/2024
GEC required to be bonded to building steel.
|
||||
Miscellaneous/Other
Carried Forward
04/01/2024
Bonding jumper to be installed in CT can.
|
||||
Miscellaneous/Other
Carried Forward
04/01/2024
Ground rods required to be installed for services.
|
||||
Electrical Final Inspection | Passed | 12/30/2024 (10:00 - 12:00) | 12/30/2024 (AM) | 12/30/2024 |