Permit Number: PREL202215105

Electrical
Finaled
01/09/2023
05/06/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Underground Electrical Inspection Partial Pass 1/26/2023 (7:00 - 8:00) 1/26/2023 (AM) 01/26/2023
Corrections:


Miscellaneous/Other
Comment Only
01/26/2023
UG for interior- ok

Electrical Rough-in Inspection Partial Pass 3/1/2023 (12:30 - 2:30) 3/1/2023 (PM) 03/02/2023
Corrections:


Miscellaneous/Other
Comment Only
03/02/2023
Partial wall RI- ok to spray foam.

Electrical Rough-in Inspection Partial Pass 3/22/2023 (12:30 - 2:30) 3/22/2023 (PM) 03/23/2023
Corrections:


Miscellaneous/Other
Comment Only
03/23/2023
Wall RI and shaft piping to roof - ok

Electrical Rough-in Inspection Partial Pass 4/4/2023 (8:00 - 10:00) 4/4/2023 (AM) 04/04/2023
Corrections:


Miscellaneous/Other
Comment Only
04/04/2023
RI for vestibule area - ok

Electrical Rough-in Inspection Passed 4/20/2023 (12:30 - 2:30) 4/20/2023 (PM) 04/20/2023
Corrections:


Miscellaneous/Other
Comment Only
04/20/2023
Wall RI for cooler area

Underground Electrical Inspection Partial Pass 5/11/2023 (12:30 - 2:30) 5/11/2023 (PM) 05/11/2023
Corrections:


Miscellaneous/Other
Comment Only
05/11/2023
UG feeder pipes to grocery- ok

Electrical Rough-in Inspection Partial Pass 6/6/2023 (8:00 - 10:00) 6/6/2023 (AM) 06/06/2023
Corrections:


Miscellaneous/Other
Carried Forward
06/06/2023
Above ceiling - ok

Electrical Rough-in Inspection Partial Pass 8/17/2023 (10:00 - 12:00) 8/17/2023 (AM) 08/17/2023
Corrections:


Miscellaneous/Other
Resolved
08/17/2023
Above ceiling - ok

Miscellaneous/Other
Carried Forward
08/17/2023
Service requires GFPE and Arc Energy reduction testing before energizing.

Miscellaneous/Other
Comment Only
08/17/2023
Sub panels inside store- ok

Electrical Final Inspection Partial Pass 9/22/2023 (10:00 - 12:00) 9/22/2023 (AM) 09/26/2023
Corrections:


Miscellaneous/Other
Comment Only
09/26/2023
Partial floor area finals- ok

Electrical Final Inspection Partial Pass 10/2/2023 (10:00 - 12:00) 10/2/2023 (AM) 10/03/2023
Corrections:


Miscellaneous/Other
Carried Forward
10/03/2023
Fault current labeling on all panels.

Miscellaneous/Other
Carried Forward
10/03/2023
Some equipment with fault current labeling has CB not properly rated for faults.

Miscellaneous/Other
Carried Forward
10/03/2023
Vent piping on roof installed in front equipment service doors. Either equipment or pipe required to be moved to allow for proper clearances.

Miscellaneous/Other
Carried Forward
10/03/2023
A safe switching procedure shall be completed for location and disconnection of the building.

Electrical Final Inspection Partial Pass 10/24/2023 (12:30 - 2:30) 10/24/2023 (PM) 10/24/2023
Corrections:


Miscellaneous/Other
Resolved
10/24/2023
Fault current labeling on all panels.

Miscellaneous/Other
Resolved
10/24/2023
Some equipment with fault current labeling has CB not properly rated for faults.

Miscellaneous/Other
Resolved
10/24/2023
Vent piping on roof installed in front equipment service doors. Either equipment or pipe required to be moved to allow for proper clearances.

Miscellaneous/Other
Carried Forward
10/24/2023
A safe switching procedure shall be completed for location and disconnection of the building.

Electrical Final Inspection Passed 11/08/2023
Corrections:


Miscellaneous/Other
Resolved
11/08/2023
A safe switching procedure shall be completed for location and disconnection of the building.

Miscellaneous/Other
Comment Only
11/08/2023
Plan attached to permit.