PREL202301798
Electrical
Finaled
WIXON PROPERTIES LLC
Alteration/Repair/Replace
Installing (1) 200amp panelboard, (1) 200amp switch and meter cut out.
02/28/2023
03/02/2023
11/26/2023
05/30/2023

Locations

Permits

Permit Number: PREL202301798

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Partial Pass 5/24/2023 (8:00 - 10:00) 5/24/2023 (AM) 05/25/2023
Corrections:


Miscellaneous/Other
Carried Forward
05/25/2023
Proper labeling required on panel and disconnect for location and fed from. Proper arc flash warning labels and panel schedule required.

Miscellaneous/Other
Carried Forward
05/25/2023
New RTU installed requires inspection.

Miscellaneous/Other
Comment Only
05/25/2023
Meter install released to Xcel.

Electrical Final Inspection Passed 5/30/2023 (Afternoon) 5/30/2023 (PM) 05/30/2023
Corrections:


Miscellaneous/Other
Resolved
05/30/2023
Proper labeling required on panel and disconnect for location and fed from. Proper arc flash warning labels and panel schedule required.

Miscellaneous/Other
Resolved
05/30/2023
New RTU installed requires inspection.