Electrical
Finaled
ENGELSMA LLOYD
Alteration/Repair/Replace
Demo some receptacles, and add two receptacles and lights.
03/07/2023
03/08/2023
11/26/2023
05/30/2023

Locations

Permits

Permit Number: PREL202302046

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Failed 3/22/2023 (8:00 - 10:00) 3/22/2023 (AM) 03/22/2023
Corrections:


Miscellaneous/Other
Carried Forward
03/22/2023
Suite 9728 R. I. Ceiling lights. Receptacles on the wall surface mounted with MC. Needs to be in EMT with water tight fittings and stand offs from the wall because of a wet location for cleaning purposes. Add GFCI receptacles within 6 ft. of sinks. Ansel system staying but not on this electrical permit. If lighted sign is added on front fascia, will need separate permit.

Electrical Rough-in Inspection Passed 3/30/2023 (8:00 - 10:00) 3/30/2023 (AM) 03/30/2023
Corrections:


Miscellaneous/Other
Comment Only
03/30/2023
Corrections with MC cable fixed- fished down the wall for clean up area.

Electrical Final Inspection Failed 4/13/2023 (12:30 - 2:30) 4/13/2023 (PM) 04/13/2023
Corrections:


Miscellaneous/Other
Carried Forward
04/13/2023
Can’t have rubber coating seal tight wiring methods above a drop ceiling. Need in use covers on the GFCI in the wash down area.

Electrical Final Inspection Partial Pass 4/18/2023 (8:00 - 10:00) 4/18/2023 (AM) 04/18/2023
Corrections:


Miscellaneous/Other
Resolved
04/18/2023
Can’t have rubber coating seal tight wiring methods above a drop ceiling. Need in use covers on the GFCI in the wash down area.

Miscellaneous/Other
Comment Only
04/18/2023
Will give a final inspection when all equipment is in and ready to open when Ansel fire system is figured out. Might need more GFCI receptacles and in use covers when areas of the bakery for cleaning are figured out.

Electrical Final Inspection Failed 5/26/2023 (7:00 - 8:00) 5/26/2023 (AM) 05/26/2023
Corrections:


Miscellaneous/Other
Carried Forward
05/26/2023
GFCI required for kitchen/ food prep area receptacles.

Electrical Final Inspection Passed 5/30/2023 (10:00 - 12:00) 5/30/2023 (AM) 05/30/2023
Corrections:


Miscellaneous/Other
Resolved
05/30/2023
GFCI required for kitchen/ food prep area receptacles.