PREL202306429
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Partial Pass | 9/7/2023 (8:00 - 10:00) | 9/7/2023 (AM) | 09/12/2023 |
Corrections:
Miscellaneous/Other
Carried Forward
09/12/2023
GEC ran inside LFMC requires bonding on both ends of conduit.
|
||||
Miscellaneous/Other
Carried Forward
09/12/2023
Available fault current labeling required on all disconnects with OCP.
|
||||
Miscellaneous/Other
Comment Only
09/12/2023
Roof top wiring - ok
Xcel contacted
|
||||
Electrical Final Inspection | Passed | 10/3/2023 (2:30 - 3:30) | 10/3/2023 (PM) | 10/03/2023 |
Corrections:
Miscellaneous/Other
Resolved
10/03/2023
GEC ran inside LFMC requires bonding on both ends of conduit.
|
||||
Miscellaneous/Other
Resolved
10/03/2023
Available fault current labeling required on all disconnects with OCP.
|
||||
Miscellaneous/Other
Comment Only
10/03/2023
Bonding and labeling - ok
Xcel contacted
|