PREL202309547
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Rough-in Inspection | Failed | 8/17/2023 (2:30 - 3:30) | 8/17/2023 (PM) | 08/17/2023 |
|
Corrections:
Miscellaneous/Other
Carried Forward
08/17/2023
Service pipe on rear of home pulled loose from meter enclosure.
Service pipes require proper support at final.
|
||||
|
Miscellaneous/Other
Carried Forward
08/17/2023
Improper wiring method on light next to front door. Old BX wiring requires proper connector and box connections to maintain EGC
|
||||
|
Miscellaneous/Other
Carried Forward
08/17/2023
Two receptacles installed and energized remove for viewing of RI.
|
||||
| Electrical Rough-in Inspection | Passed | 8/21/2023 (8:00 - 10:00) | 8/21/2023 (AM) | 08/21/2023 |
|
Corrections:
Miscellaneous/Other
Resolved
08/21/2023
Service pipe on rear of home pulled loose from meter enclosure.
Service pipes require proper support at final.
|
||||
|
Miscellaneous/Other
Resolved
08/21/2023
Improper wiring method on light next to front door. Old BX wiring requires proper connector and box connections to maintain EGC
|
||||
|
Miscellaneous/Other
Resolved
08/21/2023
Two receptacles installed and energized remove for viewing of RI.
|
||||
|
Miscellaneous/Other
Comment Only
08/21/2023
Siding RI- ok
|
||||
| Electrical Final Inspection | Passed | 8/23/2023 (10:00 - 12:00) | 8/23/2023 (AM) | 08/23/2023 |
|
Corrections:
Miscellaneous/Other
Comment Only
08/23/2023
GFCI- ok
|
||||