PREL202310039
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Rough-in Inspection | Partial Pass | 10/12/2023 (10:00 - 12:00) | 10/12/2023 (AM) | 10/12/2023 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/12/2023
R. I. Walls only for suite 180.
|
||||
| Electrical Final Inspection | Failed | 12/14/2023 (8:00 - 10:00) | 12/14/2023 (AM) | 12/14/2023 |
|
Corrections:
Miscellaneous/Other
Carried Forward
12/14/2023
One bad GFCI in kitchenette.
Fridge receptacle needs to be GFCI protected and readily accessible.
Need to have MC cables in ceiling strapped so not to touch the ceiling grid.
Need bushings on conduit for low voltage phone wires.
|
||||
| Electrical Final Inspection | Passed | 12/15/2023 (8:00 - 10:00) | 12/15/2023 (AM) | 12/15/2023 |
|
Corrections:
Miscellaneous/Other
Resolved
12/15/2023
One bad GFCI in kitchenette.
Fridge receptacle needs to be GFCI protected and readily accessible.
Need to have MC cables in ceiling strapped so not to touch the ceiling grid.
Need bushings on conduit for low voltage phone wires.
|
||||