Summary

PREL202312057
Electrical
Finaled
INTERNATIONAL PLAZA
Alteration/Repair/Replace
PO 38504 DISCONNECT WIRING FOR REMOVAL & DISPOSAL BY OTHERS, RECYCLE FLUORESCENT LAMPS, WIRE T GRINDER WHIP, FURNITURE BASE FEED, RE-SWITCH REMAINING VACANCY LIGHTS, FURNISH & INSTALL 41 FIXTURES, 1 EXIT/EMERGENCY SIGN/LIGHT, 1 PROGRAMMABLE TIMER SWITCH FOR OPEN AREA LIGHTS, 4 WALL MOUNT DIMMING OCCUPANCY SENSORS, 1 LED DIMMER FOR THE CONFERENCE ROOM, 1 CEILING MOUNT OCCUPANCY SENSOR FOR THE CONFERENCE ROOM, 1 CR OPENING, 10 PHONE/DATA OPENINGS, 7 RECEPTACLES.
10/02/2023
10/03/2023
05/12/2024
11/14/2023

Locations

Permits

Permit Number: PREL202312057

Electrical
Finaled
10/03/2023
05/12/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Failed 10/30/2023 (10:00 - 12:00) 10/30/2023 (AM) 10/30/2023
Corrections:


Miscellaneous/Other
Carried Forward
10/30/2023
Above ceiling inspection. Lighting installed ok Numerous low voltage wiring issues throughout space ceiling, fire and communications. No padding until cleaned up and reinspection is completed

Electrical Rough-in Inspection Passed w/ Conditions 11/1/2023 (10:00 - 12:00) 11/1/2023 (AM) 11/01/2023
Corrections:


Miscellaneous/Other
Resolved
11/01/2023
Above ceiling inspection. Lighting installed ok Numerous low voltage wiring issues throughout space ceiling, fire and communications. No padding until cleaned up and reinspection is completed

Miscellaneous/Other
Comment Only
11/01/2023
LV still being worked on while onsite. Still had a few locations to clean up.

Miscellaneous/Other
Outstanding
11/01/2023
Garage door opener wiring for sensors nonplenum rated. Need to be replaced with correct wiring. Verify plug for opener below ceiling. Will verify corrections at final.

Electrical Final Inspection Failed 11/9/2023 (12:30 - 2:30) 11/9/2023 (PM) 11/09/2023
Corrections:


Miscellaneous/Other
Carried Forward
11/09/2023
GFCI missing within 6’ of sink. GFCI required to be installed in a readily accessible location.

Electrical Final Inspection Passed 11/14/2023 (12:30 - 2:30) 11/14/2023 (PM) 11/14/2023
Corrections:


Miscellaneous/Other
Resolved
11/14/2023
GFCI missing within 6’ of sink. GFCI required to be installed in a readily accessible location.