PREL202312363
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Failed | 1/24/2024 (8:00 - 10:00) | 1/24/2024 (AM) | 01/24/2024 |
|
Corrections:
Miscellaneous/Other
Carried Forward
01/24/2024
New cabanas require approved NRTL listing marks.
|
||||
|
Miscellaneous/Other
Carried Forward
01/24/2024
Metal frames of cabanas required to be connected to equipotential bonding system of park
|
||||
|
Miscellaneous/Other
Carried Forward
01/24/2024
Verify GFCI protection on all lighting circuits in cabanas.
|
||||
|
Miscellaneous/Other
Carried Forward
01/24/2024
Receptacles not allowed within 6' of pools edge.
|
||||
| Electrical Final Inspection | Passed | 4/17/2025 (8:00 - 10:00) | 4/17/2025 (AM) | 04/17/2025 |
| Inspection canceled. Job wasn't quite ready. [Nelson-Thorpe\, Sarah @ 03/20/2024 1:03 PM] | ||||
|
Corrections:
Miscellaneous/Other
Outstanding
01/24/2024
New cabanas require approved NRTL listing marks.
|
||||
|
Miscellaneous/Other
Outstanding
01/24/2024
Metal frames of cabanas required to be connected to equipotential bonding system of park
|
||||
|
Miscellaneous/Other
Outstanding
01/24/2024
Verify GFCI protection on all lighting circuits in cabanas.
|
||||
|
Miscellaneous/Other
Outstanding
01/24/2024
Receptacles not allowed within 6' of pools edge.
|
||||
|
Miscellaneous/Other
Comment Only
04/17/2025
Outlets moved farther than 6’ from pool edge.
All cabanas now properly bonded to equipotential plane
Listing marks present
All receptacles and switches are now gfci protected and have weatherproof covers.
|
||||