Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 1/16/2024 (8:00 - 10:00) | 1/16/2024 (AM) | 01/16/2024 |
Corrections:
Miscellaneous/Other
Comment Only
01/16/2024
R. I. Walls break room area 2nd floor.
|
||||
Electrical Rough-in Inspection | Failed | 2/22/2024 (8:00 - 10:00) | 2/22/2024 (AM) | 02/22/2024 |
Corrections:
Miscellaneous/Other
Resolved
03/06/2024
Phase 1 -2nd floor - R. I. Ceilings - Ok
At final for phase 1 - need GFCI receptacles within 6 Feet of sinks in the Exam rooms 32-36.
Also need panel directory labeled for circuits in the area of suite 220.
Permit will stay open for Phase 2 on the 3rd floor for more R. I. - so partial final for Phase one.
|
||||
Progress Inspection | Partial Pass | 3/6/2024 (12:30 - 2:30) | 3/6/2024 (PM) | 03/06/2024 |
Corrections:
Miscellaneous/Other
Comment Only
03/06/2024
Phase 1 final on 2nd floor suite 220.
There will be 3 more phases to this permit number.
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/18/2024 (10:00 - 12:00) | 4/18/2024 (AM) | 04/18/2024 |
Corrections:
Miscellaneous/Other
Resolved
04/18/2024
Phase 1 -2nd floor - R. I. Ceilings - Ok
At final for phase 1 - need GFCI receptacles within 6 Feet of sinks in the Exam rooms 32-36.
Also need panel directory labeled for circuits in the area of suite 220.
Permit will stay open for Phase 2 on the 3rd floor for more R. I. - so partial final for Phase one.
|
||||
Miscellaneous/Other
Comment Only
04/18/2024
R. I. Walls and hard lid ceiling soffit can lights- 3rd floor phase 2.
|
||||
Electrical Rough-in Inspection | Partial Pass | 5/24/2024 (8:00 - 10:00) | 5/24/2024 (AM) | 05/24/2024 |
Corrections:
Miscellaneous/Other
Comment Only
05/24/2024
Above ceiling- ok
|
||||
Progress Inspection | Partial Pass | 6/7/2024 (8:00 - 10:00) | 6/7/2024 (AM) | 06/07/2024 |
Corrections:
Miscellaneous/Other
Comment Only
06/07/2024
Final phase 1 3rd floor.
On this permit there will be 4 phases to the 3rd floor Dermatology Expansion.
So there will be 6 more R. I. For walls and ceilings and 3 more final inspections for phases 2 , 3 and 4.
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/22/2024 (10:00 - 12:00) | 7/22/2024 (AM) | 07/22/2024 |
Corrections:
Miscellaneous/Other
Comment Only
07/22/2024
Wall RI for waiting room area.
|
||||
Electrical Rough-in Inspection | Partial Pass | 8/2/2024 (10:00 - 12:00) | 8/2/2024 (AM) | 08/02/2024 |
Corrections:
Miscellaneous/Other
Comment Only
08/02/2024
R. I. Walls 3rd floor phase 3- exam rooms.
|
||||
Electrical Rough-in Inspection | Partial Pass | 8/9/2024 (8:00 - 10:00) | 8/9/2024 (AM) | 08/09/2024 |
Above ceiling inspection | ||||
Corrections:
Miscellaneous/Other
Comment Only
08/09/2024
R. I. Ceilings 3rd floor waiting room- phase 3.
|
||||
Electrical Final Inspection | Partial Pass | 8/14/2024 (12:30 - 2:30) | 8/14/2024 (PM) | 08/14/2024 |
Corrections:
Miscellaneous/Other
Comment Only
08/14/2024
3rd floor waiting room final
|
||||
Electrical Rough-in Inspection | Partial Pass | 8/30/2024 (8:00 - 10:00) | 8/30/2024 (AM) | 08/30/2024 |
Corrections:
Miscellaneous/Other
Comment Only
08/30/2024
R. I. Walls 3rd floor Phase 3 - 4 treatment rooms.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/6/2024 (8:00 - 10:00) | 9/6/2024 (AM) | 09/06/2024 |
Corrections:
Miscellaneous/Other
Comment Only
09/06/2024
R. I. Ceilings 3rd floor Phase 3-1.
|
||||
Progress Inspection | Partial Pass | 9/26/2024 (8:00 - 10:00) | 9/26/2024 (AM) | 09/26/2024 |
Phase 3 | ||||
Corrections:
Miscellaneous/Other
Comment Only
09/26/2024
Final Phase 2 1/2 3rd floor.
|
||||
Progress Inspection | Partial Pass | 9/26/2024 (12:30 - 2:30) | 9/26/2024 (PM) | 09/26/2024 |
Phase 4 | ||||
Corrections:
Miscellaneous/Other
Comment Only
09/26/2024
R. Ceilings phase 3 for 3rd floor.
|
||||
Progress Inspection | Partial Pass | 10/11/2024 (10:00 - 12:00) | 10/11/2024 (AM) | 10/11/2024 |
Corrections:
Miscellaneous/Other
Comment Only
10/11/2024
Final phase 3 on 3rd floor exam rooms.
|
||||
Electrical Final Inspection | Passed | 10/31/2024 (7:00 - 8:00) | 10/31/2024 (AM) | 10/31/2024 |