PREL202401865
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Passed | 3/11/2024 (2:30 - 3:30) | 3/11/2024 (PM) | 03/11/2024 |
Corrections:
Miscellaneous/Other
Comment Only
03/11/2024
Wall Ri- ok
|
||||
Electrical Final Inspection | Failed | 4/16/2024 (8:00 - 10:00) | 4/16/2024 (AM) | 04/16/2024 |
Corrections:
Miscellaneous/Other
Comment Only
04/16/2024
Misc receptacle adds- ok
|
||||
Miscellaneous/Other
Carried Forward
04/16/2024
LED tape light installed under bubble wall area has an unlisted driver.
Driver required to be class 2 listed led driver.
|
||||
Electrical Final Inspection | Passed | 4/25/2024 (12:30 - 2:30) | 4/25/2024 (PM) | 04/25/2024 |
Corrections:
Miscellaneous/Other
Resolved
04/25/2024
LED tape light installed under bubble wall area has an unlisted driver.
Driver required to be class 2 listed led driver.
|
||||
Miscellaneous/Other
Comment Only
04/25/2024
Driver and lighting removed.
|