PREL202403297
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Rough-in Inspection | Partial Pass | 5/3/2024 (8:00 - 10:00) | 5/3/2024 (AM) | 05/03/2024 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/03/2024
R. I. Walls 23rd floor tenant space only.
|
||||
| Electrical Rough-in Inspection | Failed | 7/5/2024 (10:00 - 12:00) | 7/5/2024 (AM) | 07/05/2024 |
|
Corrections:
Miscellaneous/Other
Carried Forward
07/05/2024
Medium conference room has open junction boxes above the ceiling.
SE corner office the 2 - 2 X 4 lights need support wires, looks like they were cut.
The hallway by the elevator has no ceiling grid in yet.
R. I. In large conference room for receptacles on the west wall lower soffit- Ok.
|
||||
| Electrical Rough-in Inspection | Passed | 7/9/2024 (8:00 - 10:00) | 7/9/2024 (AM) | 07/09/2024 |
|
Corrections:
Miscellaneous/Other
Resolved
07/09/2024
Medium conference room has open junction boxes above the ceiling.
SE corner office the 2 - 2 X 4 lights need support wires, looks like they were cut.
The hallway by the elevator has no ceiling grid in yet.
R. I. In large conference room for receptacles on the west wall lower soffit- Ok.
|
||||
|
Miscellaneous/Other
Comment Only
07/09/2024
R. I. Ceilings Ok for lights and power only.
Fire alarm and VAV controls different contractors.
|
||||
| Electrical Final Inspection | Passed | 8/8/2024 (8:00 - 10:00) | 8/8/2024 (AM) | 08/08/2024 |