PREL202405092
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Pending | |||
Electrical Final Inspection | Failed | 5/14/2024 (8:00 - 10:00) | 5/14/2024 (AM) | 05/14/2024 |
Corrections:
Miscellaneous/Other
Carried Forward
05/14/2024
Grounding electrode conductor required to be minimum #6
|
||||
Miscellaneous/Other
Carried Forward
05/14/2024
Grounded conductor required to be bonded to service disconnects. With proper ground bar kits.
|
||||
Miscellaneous/Other
Comment Only
05/14/2024
Spoke with contractor onsite. Service connection released to Xcel.
Will reinspect the week of the 20th.
|
||||
Electrical Final Inspection | Partial Pass | 5/20/2024 (8:00 - 10:00) | 5/20/2024 (AM) | 05/20/2024 |
Corrections:
Miscellaneous/Other
Resolved
05/20/2024
Grounding electrode conductor required to be minimum #6
|
||||
Miscellaneous/Other
Resolved
05/20/2024
Grounded conductor required to be bonded to service disconnects. With proper ground bar kits.
|
||||
Miscellaneous/Other
Comment Only
05/20/2024
Issues resolved.
Xcel contacted
|