Permit Application Status

PREL202405439


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202405439
Electrical
Expired
OXBOW REALTY PARTNERS LLC
Alteration/Repair/Replace
FIB 502 Tool install
04/29/2024
05/01/2024
10/30/2024

Locations

Permits

Permit Number: PREL202405439

Electrical
Expired
05/01/2024
10/30/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
05/03/2024
Equipment evaluation required for new tool. Transformer install requires bonding or ground monitoring

Electrical Rough-in Inspection Passed 5/2/2024 (8:00 - 10:00) 5/2/2024 (AM) 05/03/2024
Corrections:


Miscellaneous/Other
Comment Only
05/03/2024
Wiring of new tool RI portion - ok Equipment evaluation required, transformer install requires either bonding or ground monitor protection.

Electrical Final Inspection Failed 5/2/2024 (8:00 - 10:00) 5/2/2024 (AM) 05/03/2024
Corrections:


Miscellaneous/Other
Carried Forward
05/03/2024
Equipment evaluation required for new tool. Transformer install requires bonding or ground monitoring