PREL202405754
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Rough-in Inspection | Passed | 6/13/2024 (8:00 - 10:00) | 6/13/2024 (AM) | 06/13/2024 |
|
Corrections:
Miscellaneous/Other
Comment Only
06/13/2024
Work all fished down walls - ok
New lighting in clouds- ok
|
||||
| Electrical Final Inspection | Partial Pass | 6/13/2024 (8:00 - 10:00) | 6/13/2024 (AM) | 06/13/2024 |
|
Corrections:
Miscellaneous/Other
Carried Forward
06/13/2024
New pendant lighting ran along roof decking requires 1 1/2” clearances from decking.
Call for reinspection when complete.
|
||||
| Electrical Final Inspection | Passed | 6/14/2024 (12:30 - 2:30) | 6/14/2024 (PM) | 06/14/2024 |
|
Corrections:
Miscellaneous/Other
Resolved
06/14/2024
New pendant lighting ran along roof decking requires 1 1/2” clearances from decking.
Call for reinspection when complete.
|
||||
|
Miscellaneous/Other
Comment Only
06/14/2024
Piping moved down from pan- ok
Unable to test exit/ em light
|
||||