Permit Application Status

PREL202405754


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202405754
Electrical
Finaled
ELDER-JONES ASSOCIATES
Alteration/Repair/Replace
New lighting for Annex remodel.
05/03/2024
05/06/2024
12/11/2024
06/14/2024

Locations

Permits

Permit Number: PREL202405754

Electrical
Finaled
05/06/2024
12/11/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Passed 6/13/2024 (8:00 - 10:00) 6/13/2024 (AM) 06/13/2024
Corrections:


Miscellaneous/Other
Comment Only
06/13/2024
Work all fished down walls - ok New lighting in clouds- ok

Electrical Final Inspection Partial Pass 6/13/2024 (8:00 - 10:00) 6/13/2024 (AM) 06/13/2024
Corrections:


Miscellaneous/Other
Carried Forward
06/13/2024
New pendant lighting ran along roof decking requires 1 1/2” clearances from decking. Call for reinspection when complete.

Electrical Final Inspection Passed 6/14/2024 (12:30 - 2:30) 6/14/2024 (PM) 06/14/2024
Corrections:


Miscellaneous/Other
Resolved
06/14/2024
New pendant lighting ran along roof decking requires 1 1/2” clearances from decking. Call for reinspection when complete.

Miscellaneous/Other
Comment Only
06/14/2024
Piping moved down from pan- ok Unable to test exit/ em light