Permit Application Status

PREL202408350


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202408350
Electrical
Finaled
SICK PRODUCT & COMPETENCE CENTER AMERICAS LLC
Alteration/Repair/Replace
***Permit extended 180 days as of 8/25/25- ok per BG*** DDC Controls Building Automation System SICK Mpls Campus Parking Ramp - Uhl 024TC137
06/27/2024
06/28/2024
02/24/2026
08/28/2025

Locations

Permits

Permit Number: PREL202408350

Electrical
Finaled
06/28/2024
02/24/2026

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Passed 8/28/2025 (10:00 - 12:00) 8/28/2025 (AM) 08/28/2025
Corrections:


Miscellaneous/Other
Comment Only
08/28/2025
Automation and controls for elevators and heaters in parking ramp - Ok All work is done in visible blue conduit to distinguish control circuits. All low voltage control circuits are protected by flexible conduit where they share space with high voltage gutters, creating a barrier.