Permit Application Status

PREL202408444


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202408444
Electrical
Finaled
JBC BLOOMINGTON LLC
Alteration/Repair/Replace
Air Conditioner replacement.
06/28/2024
07/01/2024
04/30/2025
11/01/2024

Locations

Permits

Permit Number: PREL202408444

Electrical
Finaled
07/01/2024
04/30/2025

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Failed 7/11/2024 (10:00 - 12:00) 7/11/2024 (AM) 07/11/2024
Corrections:


Miscellaneous/Other
Carried Forward
07/11/2024
AC connected to Homline Square D 20a circuit breaker. Panel is a ITE(Seimens) brand breaker must match manufactures to maintain listing requirements.

Electrical Final Inspection Passed 11/1/2024 (8:00 - 10:00) 11/1/2024 (AM) 11/01/2024
Corrections:


Miscellaneous/Other
Outstanding
07/11/2024
AC connected to Homline Square D 20a circuit breaker. Panel is a ITE(Seimens) brand breaker must match manufactures to maintain listing requirements.