PREL202502967
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Pending | |||
| Electrical Rough-in Inspection | Failed | 11/5/2025 (12:30 - 2:30) | 11/5/2025 (PM) | 11/05/2025 |
|
Corrections:
Miscellaneous/Other
Carried Forward
11/05/2025
1- Wires feeding sub panel need to be up sized for 100amps or a 90 amp breaker installed in emergency disconnect
2-fan rated boxes need to be installed in living room and dining room and anywhere that a ceiling fan may be installed in the future
3- kit small appliance circuits can not contain any lights ( Kit sink)
4- remove old romex in dining room
5-nead exterior receptacle in the front of house
6-rear exterior receptacle is damaged beyond repair, needs replacement
7-need to add receptacle near bath in basement
8-Exterior light needed on garage service door
9-Need expansion fittings on both sides of garage conduit
|
||||
| Electrical Rough-in Inspection | Passed | 11/13/2025 (8:00 - 10:00) | 11/13/2025 (AM) | 11/13/2025 |
|
Corrections:
Miscellaneous/Other
Resolved
11/13/2025
1- Wires feeding sub panel need to be up sized for 100amps or a 90 amp breaker installed in emergency disconnect
2-fan rated boxes need to be installed in living room and dining room and anywhere that a ceiling fan may be installed in the future
3- kit small appliance circuits can not contain any lights ( Kit sink)
4- remove old romex in dining room
5-nead exterior receptacle in the front of house
6-rear exterior receptacle is damaged beyond repair, needs replacement
7-need to add receptacle near bath in basement
8-Exterior light needed on garage service door
9-Need expansion fittings on both sides of garage conduit
|
||||
|
Miscellaneous/Other
Comment Only
11/13/2025
Service entrance swapped to 1awg aluminum
Fan rated boxes installed
Exterior lights and receptacles added
Expansion fittings added
I will contact Xcel for meter
|
||||