Summary

PREL202504436
Electrical
Finaled
ENGELSMA LLOYD
Alteration/Repair/Replace
Install 600A overhead service and electrical system for the construction of Salons by JC in Bloomington.
04/28/2025
05/15/2025
03/17/2026
09/18/2025

Locations

Permits

Permit Number: PREL202504436

Electrical
Finaled
05/15/2025
03/17/2026

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 5/21/2025 (10:00 - 12:00) 5/21/2025 (AM) 05/21/2025
Corrections:


Miscellaneous/Other
Carried Forward
05/21/2025
Need pictures of direct burial GEC clamp

Electrical Rough-in Inspection Partial Pass 05/22/2025
Corrections:


Miscellaneous/Other
Resolved
05/22/2025
Need pictures of direct burial GEC clamp

Miscellaneous/Other
Resolved
05/22/2025
Picture received of GEC connection

Electrical Rough-in Inspection Partial Pass 6/18/2025 (12:30 - 2:30) 6/18/2025 (PM) 06/18/2025
Corrections:


Miscellaneous/Other
Comment Only
06/18/2025
Partial wall RI- west side salon rooms, south side window wall East side wall only Ok to cover those ares

Miscellaneous/Other
Comment Only
06/18/2025
Will need remainder of walls and ceiling inspection

Electrical Rough-in Inspection Partial Pass 6/26/2025 (10:00 - 12:00) 6/26/2025 (AM) 06/26/2025
Corrections:


Miscellaneous/Other
Comment Only
06/26/2025
Wall RI ok Check ground screws next inspection

Electrical Rough-in Inspection Partial Pass 7/9/2025 (2:30 - 3:30) 7/9/2025 (PM) 07/09/2025
Corrections:


Miscellaneous/Other
Comment Only
07/09/2025
Service-ok Hard lid ok

Electrical Rough-in Inspection Passed 8/15/2025 (12:30 - 2:30) 8/15/2025 (PM) 08/15/2025
Corrections:


Miscellaneous/Other
Comment Only
08/15/2025
Ceiling rough in ok Limited energy by Sterling? Fire permit? Grounding electrodes in ceiling are THHN - not plenum rated , talk to Jim

Electrical Final Inspection Passed 9/18/2025 (8:00 - 10:00) 9/18/2025 (AM) 09/18/2025
Corrections:


Miscellaneous/Other
Resolved
09/18/2025
One rooftop has OCP max of 70. It has a 80 breaker Electrician sent me a pic of the correction