PREL202505891
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Failed | 7/17/2025 (10:00 - 12:00) | 7/17/2025 (AM) | 07/17/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
07/17/2025
New AC unit. Upon Inspection, AC unit max fuse or ckt breaker 20 amps.
25 amp fuses were found in disconnect.
Could not verify ckt breaker as nobody answered door.
Update fuses to correct size or verify breaker is 20 amp. A photo will suffice.
Knocked twice and rung doorbell.
|
||||
| Electrical Final Inspection | Passed - Virtual or Photo Inspection | 7/24/2025 (10:00 - 12:00) | 7/24/2025 (AM) | 07/24/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
07/24/2025
New AC. Correction from last visit. Max fuse/breaker 20amps. Verified protection at the electrical panel
|
||||