Summary

PREL202505891
Electrical
Finaled
JBC BLOOMINGTON LLC
Alteration/Repair/Replace
AC Replacement.
05/29/2025
05/29/2025
01/13/2026
07/24/2025

Locations

Permits

Permit Number: PREL202505891

Electrical
Finaled
05/29/2025
01/13/2026

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Failed 7/17/2025 (10:00 - 12:00) 7/17/2025 (AM) 07/17/2025
Corrections:


Miscellaneous/Other
Comment Only
07/17/2025
New AC unit. Upon Inspection, AC unit max fuse or ckt breaker 20 amps. 25 amp fuses were found in disconnect. Could not verify ckt breaker as nobody answered door. Update fuses to correct size or verify breaker is 20 amp. A photo will suffice. Knocked twice and rung doorbell.

Electrical Final Inspection Passed - Virtual or Photo Inspection 7/24/2025 (10:00 - 12:00) 7/24/2025 (AM) 07/24/2025
Corrections:


Miscellaneous/Other
Comment Only
07/24/2025
New AC. Correction from last visit. Max fuse/breaker 20amps. Verified protection at the electrical panel