PREL202507249
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 7/14/2025 (10:00 - 12:00) | 7/14/2025 (AM) | 07/14/2025 |
Corrections:
Miscellaneous/Other
Comment Only
07/14/2025
RI for walls OK
2 new panels going in with transformer. Will need applicable calculations.
|
||||
Above Ceiling Inspection | Passed | 7/31/2025 (10:00 - 12:00) | 7/31/2025 (AM) | 07/31/2025 |
Corrections:
Miscellaneous/Other
Comment Only
07/31/2025
Above ceiling OK
Still waiting on some walls for wires to be routed
|
||||
Electrical Rough-in Inspection | Passed | 9/24/2025 (10:00 - 12:00) | 9/24/2025 (AM) | 09/24/2025 |
Electrical Final Inspection | Partial Pass | 9/24/2025 (10:00 - 12:00) | 9/24/2025 (AM) | 09/24/2025 |
Corrections:
Miscellaneous/Other
Comment Only
09/24/2025
Final for Columbia OK.
All lighting and drivers are UL listed and Class 2 where applicable.
Final is contingent on a few photos for panel schedule labeling, a few new receptacles, and store front signage.
|
||||
Electrical Final Inspection | Passed | 9/24/2025 (3:30 - 4:00) | 9/24/2025 (PM) | 09/24/2025 |
Corrections:
Miscellaneous/Other
Comment Only
09/24/2025
Final for MOA Columbia.
Store signs have been installed.
All receptacles now installed.
Panel is now labeled.
|