PREL202509723
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Failed | 8/18/2025 (12:30 - 2:30) | 8/18/2025 (PM) | 08/18/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
08/18/2025
New AC unit. Max fuse or breaker size 20 amps. Fuses in disconnect were 30 amps. Electrical panel is not labeled and can not identify AC breaker. Will need 20 amp fuses or labeled 20 amp breaker.
|
||||
| Electrical Final Inspection | Passed | 11/6/2025 (10:00 - 12:00) | 11/6/2025 (AM) | 11/06/2025 |