PRFS201706360
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Rough-in Inspection | VOID | 08/25/2017 | ||
Per Anne and Kelly, seems to be duplicate workflow activities - voided. ajacobson 08/25/2017 10:15 AM | ||||
Fire Inspection Final | VOID | 08/25/2017 | ||
Per Anne and Kelly, seems to be duplicate workflow activities - voided. ajacobson 08/25/2017 10:15 AM | ||||
Fire Rough-in Inspection | Partial Pass | 8/30/2017 (10:00 - 12:00) | 8/30/2017 | 08/30/2017 |
Corrections:
Heads too close to air diffuser (minimum 2ft)
Outstanding
08/30/2017
Heads too close to air diffuser (minimum 2ft) multiple heads too close to diffusers
|
||||
Heads obstructed
Outstanding
08/30/2017
Heads obstructed. Head moved by hvac tech.
|
||||
Fire Inspection Final | Failed | 10/9/2017 (Afternoon) | 10/9/2017 | 10/09/2017 |
Corrections:
Heads too close to air diffuser (minimum 2ft)
Carried Forward
10/09/2017
Heads too close to air diffuser (minimum 2ft)
|
||||
Fire Inspection Final | Passed | 10/10/2017 | ||
Corrections:
Heads too close to air diffuser (minimum 2ft)
Outstanding
10/09/2017
Heads too close to air diffuser (minimum 2ft)
|